AEROVITAL
Original operating instructions
06.2018
Programming
P1
Pollen protection
The air throughput level can be adjusted using the buttons
or
the remote control, or manually using the button on the
AEROVITAL (see „Basic functions“ see page 16).
P2
Humidity control
The AEROVITAL vents continuously in basic ventilation mode and automatically switches the air throughput level higher as
soon as the defined values have been exceeded.
• The air throughput level (1 to 4) for the basic ventilation can be freely selected
• The desired room humidity can be set to a value between 30% and 90%.
Programming example
The AEROVITAL should operate with air throughput level 2 in basic ventilation mode and automatically increase the air
throughput level from a room air humidity of 58% upwards.
Step
Button
(press briefly)
Function
Display
1
P2
hold down
approx. 5
seconds
A flashing value for the relative air humidity appears in the display.
Factory setting: 55%.
2
or
press briefly or
hold down
The numerical value is increased (
+
) or reduced (
—
) in single
increments
3
P2
A flashing fan symbol appears in the display.
4
or
press briefly or
hold down
The air throughput level for the basic ventilation is increased (
+
) or
reduced (
—
) in single increments
5
P2
The new values are saved (the display flashes 2x briefly).
• The program (P2) will now run with the newly set values.
• The display indicates the current measured values for room temperature and humidity.
• When the P2 button is pressed briefly, the programmed values will be displayed for approx. 3 seconds.