25-pole male submin D connector
X30
Pin
I/O
Name
Meaning
1
I
IN0
Switch on
2
I
IN1
Start / Stop
3
I
IN2
Error reset
4
I
IN3
Speed direction
5
I
IN4
Configuration 1/2
6
I
IN5
External hardware OK
7
n.c.
8
n.c.
9
O
UA+
Speed pulse , 6 pulses per motor revolu‐
tion
10
O
UA-
Speed pulse output -, 6 pulses per motor revolu‐
tion
11
I/O
GND
Ground
12
I/O
GND
Ground
13
I/O
GND
Ground
14
O
OUT0
Programmable digital output 1
15
O
OUT1
Programmable digital output 2
16
O
OUT2
Programmable digital output 3
17
O
OUT3
Programmable digital output 4
18
O
OUT4
Programmable digital output 5
19
O
OUT5
Programmable digital output 6
20
n.c.
21
n.c.
22
n.c.
23
I
PTC0
Do not wire
24
O
+24V
25
O
+24V
Stud bolt flange: max. tightening torque = 0.7 Nm
Related topics
Connection examples: "X30 – Digital Inputs / Outputs", page 53
8.9.1
Inputs
Switch on
When this input is activated, the control of the frequency converter is connected to
allow power transmission to the motor. The holding current is activated, if programmed.
The motor will be accelerated as soon as the start signal and a corresponding refer‐
ence value are received.
Start / Stop
The function input “Start/Stop” permits the start or stop of the frequency converter.
▶
Start = +24 V
▶
Stop = 0 V
W
Connectors
FC2 - Frequency converter 02192100xy
39
8
Summary of Contents for FC2
Page 4: ...Chapter Overview W 4 FC2 Frequency converter 02192100xy ...
Page 8: ...Content W 8 FC2 Frequency converter 02192100xy ...
Page 12: ...General Information W 12 FC2 Frequency converter 02192100xy 2 ...
Page 22: ...Unit Assembly Complying EMC W 22 FC2 Frequency converter 02192100xy 4 ...
Page 30: ...Technical Data W 30 FC2 Frequency converter 02192100xy 7 ...
Page 48: ...Connectors W 48 FC2 Frequency converter 02192100xy 8 ...
Page 70: ...Safety Circuit Restart Lock STO W 70 FC2 Frequency converter 02192100xy 12 ...