4
Unit Assembly Complying EMC
The EU guidelines for electromagnetic compatibility (EMC) must be consid‐
ered for the initial operation of all SIEB & MEYER devices.
The manual "EMC Guidelines" is available in German and English and includes:
▶
EMC rules
▶
information regarding the professional grounding and wiring
▶
safety-relevant aspects
▶
extracts from the EMC product standard
▶
possibilities for the connection to different supply system types
Availability:
▶
www.sieb-meyer.de/downloads.html
4.1
Emission of Line and Field Interferences
According to Category C3
According to the EMC product standard DIN EN 61800-3, chapter 6 (emission of line
interferences), this device meets the interference limit values of the category C3.
Requirements
▶
The device is equipped with basic interference elimination functions via an inte‐
grated line filter.
If motor cables longer than 5 m are used, an external line filter may be required.
For detailed information on mounting and connecting line filters refer to the manual
"Unit Assembly complying EMC".
▶
If no internal line filter is provided, an external line filter must be used to reach the
category C3.
NOTICE
Connection of line filters
Consider the connection instructions of the line filter manufacturer to ensure suffi‐
cient filter effect.
Appropriate line filters are provided on demand by SIEB & MEYER (see
section 13.A.1.2 "Line Filters by TDK & EPCOS Group", page 71
).
For detailed information on the used device refer to the section "Technical
Data".
NOTICE
High-frequency interferences during the use of the device in a public mains
High-frequency interferences may occur, if the device is used in a public mains
which supplies residential areas. These interferences may disturb the functioning
of other devices.
Do not use the device in a public mains or ensure appropriate interference
suppression measures.
W
Unit Assembly Complying EMC
FC2 - Frequency converter 02192100xy
21
4
Summary of Contents for FC2
Page 4: ...Chapter Overview W 4 FC2 Frequency converter 02192100xy ...
Page 8: ...Content W 8 FC2 Frequency converter 02192100xy ...
Page 12: ...General Information W 12 FC2 Frequency converter 02192100xy 2 ...
Page 22: ...Unit Assembly Complying EMC W 22 FC2 Frequency converter 02192100xy 4 ...
Page 30: ...Technical Data W 30 FC2 Frequency converter 02192100xy 7 ...
Page 48: ...Connectors W 48 FC2 Frequency converter 02192100xy 8 ...
Page 70: ...Safety Circuit Restart Lock STO W 70 FC2 Frequency converter 02192100xy 12 ...