Cooling Signal Output
Values: Normal (default)/Inverted
Set to Normal when using a hydraulic cooling pump.
Should be set to Inverted when using an electrical cooling pump with
a 10 2380A-12/24V relay box
SETUP cont.
Cooling Power Save
Values: ON (default)/OFF
ON sets the Cooling Pump into power save mode,which means the
Cooling Pump output is dropping to 0 volt when the oil pressure is be-
low 10 bar for more than 10 seconds (Cooling Pump are turned OFF).
Tank Monitor
Values: ON (default)/OFF
ON is when you have a tank monitor, oil level and Oil temp sensor.
OFF is when you do not have a tank monitor and the display will show
0°C and no alarm for high temperature or low level will not be trans-
mitted on the S-link.
Instance
Values: --(default)/PORT/STARBOARD
Setting the PHC024 tank controller instance. For a mono hull boat
the instance should be ”--“. If you have an catamaran with two
PHC024 controllers then the one in the port hull should be set as
“PORT” and the one in the starboard hull as “STARBOARD”. This
way the two controllers are shown in the panel display as two
different oil tanks to monitor.
Main Switch
Press the button below
to return to the previous menu.
Press the button below
to edit the selected parameter.
Parameter value will start to blink, use joystick to alter value.
Press the button below
to save edited parameter to device
Press the button below
to cancel editing without saving.
Location
Values: BOW/STERN/BOW-STB/STERN-STB
Set the location for selected device. Use BOW or STERN in a conven-
tional thruster system. In a system with two bow or stern thrusters
(i.e a catamaran), use BOW or STERN for port thruster, BOW-STB or
STERN-STB for starboard thruster
Cooling Pump
Values: Always Running/Temp Controlled(default)
When the option “Temp Controlled” is selected, the cooling pump will
start when oil temperature exceeds 50°C and stop when the oil tem-
perature goes below 40°C.
On systems with two oil tanks, this setting will apply to both tanks.