CONNECTING THE ELECTRICAL SYSTEMS 

The Solarstream is designed for single phase 230~240 V A.C. 50 Hz supply, max load 1400 watt.  Australian Standard AS/
NZ 3000 or AS/NZ 3006 Wiring Code and local supply authority regulations apply.

The Heat Pump should be plugged into standard day rate power points, or alternatively arrangements may be made with an 
electrician to have the power lead directly wired into an off-peak supply at the main circuit board.  Allow for a 10 amp power 
supply with circuit breaker. 

The Solarstream does not have an electrical booster element.

The Solarstream is supplied with a thermostat on the side of the Water Tank, behind the upper cover, to regulate the water 
temperature and a manual reset, over-temperature safety cut-out located on the side of the Heat Pump to protect the Heat 
Pump; these devices regulate the water temperature.  Under no circumstances, should the Solarstream be operated without 
both of these devices being in circuit. 

The wiring loom connection between the Heat Pump and the Water Tank is standard 3 metres in length, designed for 

 

 

230~240 volt ac power.  It is a 1.5 mm

 2

 cable, protected in UV resistant flexible conduit. 

Fit the wiring loom through the cable hole in top inspection cover on the Water Tank and secure with the conduit gland 

 

 

and lock nut.  Ensure the conduit gland is tight so cable cannot pull out.
Heat Pump connection:  Connect the screw down spade lugs to the heat pump thermostat connection terminal, and the
earth wire to the earth lug as in Fig A below.
Water Tank connection:  Connect the push on connectors to the tank thermostat and the earth wire to the earth lug as in Fig B below.

 

It is recommended that cable ties be used to tie the wiring loom to the refrigerant lines.

 

Where refrigerant line extension kits are used (refer page 4) these kits are supplied with matching extension thermostat 

 

 

  wiring looms. 

Never attempt to join or extend a Solarstream wiring loom. 

 

Do not connect the thermostat directly to an external power outlet.  The power source must be derived from the Heat Pump

 

 

 

  via the wiring loom.  Replacement of the wiring loom should be undertaken only by a qualified electrician or authorised 
  Solarstream service technician.
A wiring diagram is located inside the plastic side cover of the heat pump (a detailed wiring diagram is located under heat 
pump lid for maintenance).

Push on connectors
Earth to Earth lug
Ensure earth 
connection is tight.

Thermostat Connection 
onto terminals 1 & 2
Earth to Earth lug

Thermostat cable inserted 
and secured under cable 
clamp.

NOTE:
WATERPROOF SOCKET OUTLETS

Use  only  a  high  quality  IP53 
rated weather protected switched 
socket outlet.

5

Fig B: Thermostat Connection

Fig A: Heat Pump Connection

HEAT PUMP WIRING DIAGRAM

Summary of Contents for 264SSBD

Page 1: ...lly before undertaking the installation of a Siddons Solarstream Heat Pump Water Heater INSTALLATION AND USER MANUAL INSTALLERS Models Domestic 264SSBD 327SSAD Commercial 327SSAC3 AC4 AC5 AC6 www sidd...

Page 2: ...ection for the Solarstream Heat Pump Water Heater if shelter is available such as an overhanging eave it is a good idea to use it The Heat Pump unit is designed to be installed outside In cold conditi...

Page 3: ...and Pressure and Temperature P T relief valve Ensure the specification label is visible Installation must comply with Australian Standard AS NZS 3500 4 and any local authority regulations OUTDOOR For...

Page 4: ...NCE APART The maximum length of refrigerant line to be connected to the Heat Pump is 9 metres E g 2 metre standard 7 metre extension total 9 metres max Drwg A REFRIGERANT LINES IN DUCTS WALLS OR SURFA...

Page 5: ...ill feel some resistance when the metal diaphragms are punctured to facilitate refrigerant flow keep tightening until you feel the O Ring seal fully seated otherwise gas will leak under the high opera...

Page 6: ...230 240 volt ac power It is a 1 5 mm2 cable protected in UV resistant flexible conduit Fit the wiring loom through the cable hole in top inspection cover on the Water Tank and secure with the conduit...

Page 7: ...ump unit Check the Heat Pump continues to run for at least 20 minutes on first start up Warm water should be evident at hot taps in about 60 minutes Check firstly that the Heat Pump is connected to an...

Page 8: ...ndicated period from the date of the original purchase Should a part of the complete Water Tank component be replaced during this period only the balance of the original warranty will continue to rema...

Reviews: