16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
0
250
500
750
1000
1250
1500
Input voltage U [V]
L
o
a
d
r
e
s
is
ta
nc
e
R
[
Ω
]
Permitted range up to 80 °C
Additional permitted range up to 65 °C
Figure 23: Permissible load resistances TMx88A
7.4.2
Load resistance TMx88B
In the figure (
), the permissible load resistance based on the input voltage
for the operating range up to 80 °C is shown in blue. Within a restricted operating
range up to 65 °C, combinations of input voltage and load resistance from the area
shown in gray are also permitted.
Table 14: Minimum, typical, and maximum load resistances TMx88A
U
dd
[V]
R
L
min. [
Ω
] @ Ta
max
=
65 °C
R
L
min. [
Ω
] @ Ta
max
=
80 °C
R
L
max. [
Ω
]
16
0
280
450
24
270
740
850
28
510
970
1050
35
930
1370
1400
CONNECTION
7
8019053/1EF6/2021-12-13 | SICK
O P E R A T I N G I N S T R U C T I O N S | TMS/TMM88, TMS/TMM55
25
Subject to change without notice