Specifications
l
Stop longer than the restart timeout (safeRS3 Designer >
Configuration
).
l
Stop in several different points, with special attention to the areas in
close proximity to the sensor and any blind spots (see
).
l
Stop standing as well as laid down.
Example 2
Starting
conditions
l
Protective field dependency:
Independent mode
l
Machinery in safe conditions
l
Two protective fields configured (protective field 1 and protective field 2)
l
Both the safety outputs (detection signal 1 and detection signal 2)
deactivated
Validation
procedure
1. Stand still in protective field 1.
2. Check that the system maintains only the specific safety output
deactivated (see
Validate the system with safeRS3 Designer below
).
3. Repeat step 1 and 2 for protective field 2.
4. If the safety outputs do not remain deactivated (see
).
7.3.5
Example of stopping points
Stopping points for 100° field of view
7.3.6
Validate the system with safeRS3 Designer
WARNING
When the validation function is active, the system response time is not guaranteed.
The safeRS3 Designer application is helpful during the safety functions validation phase
and allows the sensors' actual field of view to be checked based on their installation
position.
1. Click
Validation
: the validation starts automatically.
2. Move in the monitored area as indicated in
Validate the access detection function on
and
Validate the restart prevention function on the previous page
3. Check that the sensor behaves as expected.
4. Check that the distance and the angle where the motion is detected are the
expected values.
7 INSTALLATION AND USE PROCEDURES
8027489/2022-03-01 | SICK
Subject to change without notice
O P E R A T I N G I N S T R U C T I O N S | safeRS3