O P E R A T I N G I N S T R U C T I O N S | safeRS3
8027489/2022-03-01 | SICK
Subject to change without notice
7 INSTALLATION AND USE PROCEDURES
7.3.7
Troubleshooting validation
Cause
Solution
Presence of objects
obstructing the field of
view
If possible, remove the object. Otherwise, implement additional safety
measures in the area where the object is present.
Position of sensors
Position the sensors to ensure that the monitored area is adequate for
the dangerous area (see
).
Inclination and
installation height of
one or more sensors
1. Change the inclination and installation height of the sensors to
ensure that the monitored area is adequate for the dangerous
area, (see
).
2. Note or update the inclination and installation height of the
sensors in the printed configuration report.
Inadequate restart
timeout
Change the restart timeout through the safeRS3 Designer application
(
Configuration
> select the affected sensor and protective field)
7.4
Manage the configuration
7.4.1
Configuration reports
After changing the configuration, the system generates a configuration report with the
following information:
l
configuration data
l
unique checksum
l
date and time of configuration change
l
name of computer in which the change was inserted
The reports are documents that cannot be changed and can only be printed and signed
by the machinery safety manager.
7.4.2
Change the configuration
WARNING
The system is disabled during configuration. Prepare opportune safety measures in the
dangerous area protected by the system before configuring the system.
1. Start the safeRS3 Designer application.
2. Click
User
and enter the admin password.
3. Depending on what you want to change, follow the instructions below:
To change...
Then...
Monitored area
and sensors
configuration
Click
Configuration
System
sensitivity
Click
Settings
>
Sensors
Node ID
Click
Settings
>
Node ID Assignment