Figure 10: Signal pathways when the function is not used
Instead, the signal
Static 1
must be connected to Input 1 and signal
Static 0
connected
to the remaining inputs. In this configuration, Timing Set 1 is permanently selected. The
Timing Set must be configured as described in
"Configuration of Sequence monitoring",
and
"Configuration of Time monitoring", page 31
.
When the Timing Set Selection function is used, the number of timing sets must be
specified. The same number of S301.x signals must be connected to the
User mode
switch
function block. Two timing sets are configured in the following example (n=2).
Figure 11: Signal pathways when the function is used with 2 timing sets
In this case the signals must be connected to the input with the same numbering, pro‐
ceeding in sequence. All remaining inputs of the operating mode selector switch func‐
tion block must be connected to the signal
Static 0
.
All selected timing sets must be configured as described in
"Configuration of Time monitoring", page 31
.
WARNING
Changing the connections of the signals for the Timing Set Selection function is an
exception during configuration. It is not permitted to change any other connections in
the logic for this safety system since this could impair safety and functioning.