Minimum
Typical
Maximum
At 4 σ
± 80 mm
At 5 σ
± 99 mm
Flatness of the scan field at 5.5 m
± 70 mm
Flatness of the scan field at 7 m
± 88 mm
Warning field range (radial)
Approx. 20
m
1)
49 m
Distance measurement range
49 m
Number of multiple samplings (can be configured
via CDS)
2
16
Power-up delay
9 s
20 s
Restart after (can be configured)
2 s
60 s
1)
For objects with 20% radiance factor.
Electric
Table 30: Electric
Minimum
Typical
Maximum
Safety laser scanner
Supply voltage (SELV)
1)
17.5 V
24 V
28.8 V
Permissible residual ripple
± 5%
Heating
Supply voltage (SELV) (full heating performance
only at nominal voltage)
21.6 V
24 V
26.4 V
Permissible residual ripple
± 5%
Current required, cyclic (note voltage drop on the
supply cable)
4 A
Start-up current
2)
2 A
Operating current without output load
3)
0.6 A
0.8 A
Operating current with maximum output load
3)
2.2 A
2.3 A
Power consumption without output load
3)
14 W
19 W
Power consumption with maximum output load
3)
53 W
55 W
Power consumption in standby mode or park mode
without output load
14 W
19 W
Electrical connection
16-pin plug with screw-type terminals
3 × PG11 cable gland for cable diameter
5-12 mm
Screw terminal technical data
Rigid wire cross-circuit
0.14 mm²
1.5 mm²
Flexible wire cross-circuit
4)
0.14 mm²
1.0 mm²
American wire gage (AWG)
26
16
Wire stripping length
5 mm
Screw tightening torque
0.22 Nm
0.25 Nm
Cable length for power supply tolerance ± 10%
At wire cross-section 1 mm²
50 m
with a wire cross-section of 0.5 mm²
25 m
with a wire cross-section of 0.25 mm²
12 m
Cable length for power supply tolerance ± 5%
TECHNICAL DATA
12
8012029/ZA20/2019-11-14 | SICK
O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store
109