7.12.3
Simultaneous monitoring
Overview
Using simultaneous monitoring, the S3000 can monitor two field sets at the same time
(e.g., a hazardous area on the left and a hazardous area on the right) within a monitor‐
ing case.
Important information
NOTE
On the S3000, simultaneous monitoring can only be configured in the dual field mode
or in the dual protective field mode (
see "Monitoring cases", page 19
).
Approach
1.
On the
Resolution/field mode
tab, select either the
Dual
or
Dual protective fields
field
mode.
2.
On the
Resolution/field mode
tab, select the
Simultaneous field evaluation
option.
3.
If you evaluate the status of the protective fields using Flexi Soft, then on the
lution/field mode
tab first select the
Transfer unallocated fields as interrupted
option.
If the
Dual protective fields
field mode was selected, then the
Transfer unallocated fields
as interrupted
option is selected automatically.
4.
On the
Cases
tab, select a further field set as a simultaneous field set within the
relevant monitoring case.
On a system with one S3000, the first protective field in both field sets acts on the
internal OSSDs on the S3000. In a system with several devices connected via EFI, the
two field sets can act on different OSSDs.
Further topics
•
•
7.12.4
Checking the monitoring case switching
To check the switching between monitoring cases, configure a series of monitoring
cases. Either an arbitrary sequence, a unique sequence, or two alternative sequences
can be defined.
•
Arbitrary sequence: It is allowed to switch from one monitoring case to any other
defined monitoring case.
•
Unique sequence: It is only allowed to switch from a monitoring case to another
specifically defined monitoring case.
•
Alternative sequence: It is allowed to switch from a monitoring case to one of two
specifically defined monitoring cases.
NOTE
Use the monitoring case switching check as an additional check on the control. For
example, to detect deviations of a vehicle from a corridor, or deviations of a system
from the prescribed production process.
Figure 57: Schematic representation of monitoring case switching - arbitrary sequence
7
CONFIGURATION