With surface mounting: mount the sensor in the fixed part of the protective
device:
Figure 9: Flush mounting
Tightening torque: 1 Nm.
3.
Set cover plate on the sensor.
4.
Tighten the fixing screws. Tightening torque: 0.8 Nm.
Mounting the actuator
1.
Align the actuator to the mounted sensor.
2.
Mount the actuator on the moving part of the protective device (e.g., door) with 4 x
M4 screws. Tightening torque: 1 Nm. Use disposable screws if possible.
°
Maximum deviation between sensor and actuator: 5 mm.
°
Maximum angle between sensor and actuator when protective device is
closed: 3°
≤ 3°
Figure 10: Maximum angle between sensor and actuator
3.
Cover drill holes of the actuator with protective caps.