Using other safety switches
NOTE
In a cascade, other safety switches within the cascade can also be used via special T-
connectors as long as the connections are structured as follows:
8
2
3
4
5
7
1
6
Table 3: Device connection pin assignment (male connector, M12, 8-pin, A-coded)
Pin
Wire color
1)
Designation
Description
1
White
–
–
2)
2
Brown
+24 V DC
Safety switch voltage supply
3
Green
N. c.
or
+24 V DC
Not connected
or
Voltage supply for locking device
3)
4
Yellow
In 2
OSSD 2 input
5
Gray
OSSD 1
OSSD 1 output
6
Pink
OSSD 2
OSSD 2 output
7
Blue
0 V
0 V DC voltage supply
8
Red
In 1
OSSD 1 input
1)
Applies to the extension cables recommended as accessories.
2)
Pin 1 is not assigned on T-connector. Safety switch signals to pin 1 are not relevant for the cascade (
).
3)
The locking device must function in accordance with the power to lock principle.
Additional voltage supply
The voltage drop in the cascade must be checked so that the defined minimum voltage
is still applied to each safety switch. If the defined minimum voltage is no longer
applied to a safety switch, a node for voltage supply must be integrated. The node for
voltage supply must be integrated in the direction of the safe evaluation unit, as close
as possible to the relevant switch in the cascade.
Number of safety switches
The maximum number of safety switches depends on the following factors:
•
Applied supply voltage
•
Length of cables used
•
Cable cross-section of cables used
•
Load current
•
Nodes for voltage supply
•
Required performance level (
)
The number of safety switches in a cascade influences the response time of the system
(
).
The maximum number of safety switches in a cascade changes depending on the total
length of cable as follows:
4
PROJECT PLANNING
18
O P E R A T I N G I N S T R U C T I O N S | MLP1