OP E R A T I N G   I N S T R U C T I O N S  | MICS3/OS3 electr. protection hood

Subject to change without notice

5

COMMISSIONING 

5.2

Safety switch

The IME2S safety switch is operated with 24 V DC and provides a signal when the protec

-

tion hood is open (end position).

Fig. 15: Protection hood closed

Protection hood open (end position)

5.2.1

Signal release for laser scanner

The signal for the laser scanner may only be released when the protection hood has 

reached the end position.

The signal of the safety switch must be switched with a logic operation.

If both are fulfilled, the release (e.g. for a move command) takes place and the laser 

scanner is active.

Legend

1

Side guide

2

Screw head

3

Safety switch 

a

2 mm ± 0.5

Summary of Contents for MICOS3

Page 1: ...MMMI MMMOPERATING INSTRUCTIONS OPE RATI NG INSTR UCTIO NS MICS3 OS3 electr protection hood...

Page 2: ...cted by copyright The associated rights are reserved by SICK AG Reproduction of this document or parts of this document is only permissible within the limits of the statutory provisions of copyright l...

Page 3: ...8 2 6 Warning symbols on the system components 8 2 7 Mandatory symbols 9 2 8 Safety notes 9 3 Product Description 11 3 1 Safety switch 12 3 2 Cable fasteners 12 3 3 Technical data 13 3 4 Mounting kit...

Page 4: ...CONTENT 4 8025999 V1 0 2021 02 SICK OP ER A T ING INST R U CT IO NS MICS3 OS3 electr protection hood Subject to change without notice...

Page 5: ...uring the life cycle Must be made available to all those who work with it Must be read through carefully and it must be ensured that the contents are fully understood Note Applicable standards and reg...

Page 6: ...he actual design Document ID Product Manufacturer outdoorScan3 oS3 8023151 outdoorScan3 Core I O SICK 8021154 outdoorScan3 EtherNet IPTM SICK microScan3 Core MICS3 Core only for indoor use 8016345 mic...

Page 7: ...MICS3 OS3 electr protection hood disconnect the voltage supply and secure it against being switched on again Follow local regulations Follow all local regulations relating to working with electrical...

Page 8: ...nts Warning labels must not be removed or covered up If labels are missing these must be affixed Damaged labels must be replaced DANGER Identifies a situation presenting danger which will lead to deat...

Page 9: ...y crushing When working on the protection hood disconnect the voltage supply and secure it against being switched on again Wear appropriate safety gloves WARNING Invisible laser radiation on safety la...

Page 10: ...10 8025999 V1 0 2021 02 SICK OP ER A T ING INST R U CT IO NS MICS3 OS3 electr protection hood Subject to change without notice 2 SAFETY INFORMATION...

Page 11: ...l movements hood closed e g from salt spray water spray or swirling dirt particles The protection hood is opened and closed electrically Fig 1 Components of the protection hood Legend 1 Hood removable...

Page 12: ...ection hood position This ensures that the open protection hood does not affect the scanning field Fig 2 Safety switch 3 2 Cable fasteners Cable fasteners should be laid as shown in Fig 3 Fig 3 Cable...

Page 13: ...g safety laser scanner under the hood SICK part number 2073851 Fig 4 Mounting kit 1a Material Stainless steel aluminum Dimensions when in closed status width x height x length 217 x 232 x 284 mm Commu...

Page 14: ...ting bracket For information on mounting the safety laser scanner to mounting kit 1a please refer to the relevant SICK operating instructions see Chapter 1 5 Additional technical documentation informa...

Page 15: ...6 an opening must be provided for the supply connection of the M12 4 pin A coded male connector The male connector requires an opening in the customer object machine wall with a diameter of at least 4...

Page 16: ...ctor are available for flexible connection Fig 7 Mounting plate M12 male connector connection variants Fig 8 Mounting plate Legend 1 M12 male connector to the rear 2 M12 male connector to the right 3...

Page 17: ...ning the protection hood in relation to the scan plane Provided by the customer Fig 10 Example of interface dimensional drawing Important note The carrier unit on the customer object must be stable en...

Page 18: ...ructions Seal unused connections with sealing caps Connect the cables to the safety laser scanner Observe cable routing For tightening torque of plug connector and protective caps see the laser scanne...

Page 19: ...coded male connector Mount protection hood and fasten by hand with knurled screws Installation of the protection hood is complete 4 4 M12 4 pin A coded male connector The M12 4 pin A coded male conne...

Page 20: ...ject to change without notice 4 INSTALLATION 4 4 1 Contact assignment Fig 13 M12 male connector pin arrangement circuit diagram contact assignment The actuator motor is connected to pin 1 and 2 Pin 1...

Page 21: ...sing circuit Fig 14 Example internal circuitry DC motor pole reversing circuit Note Only qualified persons with the relevant technical expertise are permitted to work on the system Legend 1 Relay 2 x...

Page 22: ...open end position Fig 15 Protection hood closed Protection hood open end position 5 2 1 Signal release for laser scanner The signal for the laser scanner may only be released when the protection hood...

Page 23: ...5 M6 Disconnect the protection hood from the voltage Remove hood Disconnect and remove the safety laser scanner connections Disconnect M12 male connector If access is difficult disassemble the unit fr...

Page 24: ...tr protection hood Subject to change without notice 6 MAINTENANCE Use spanner SW19 to loosen and remove the locking nut on the M12 male connector Safely store locking nut Fig 16 M12 male connector on...

Page 25: ...NS MICS3 OS3 electr protection hood Subject to change without notice MAINTENANCE 6 Loosen and remove the M4 screws on the mounting bracket using Allen wrench SW3 Fig 18 M4 screws on mounting bracket P...

Page 26: ...d unit to the support unit and connect it Restore the voltage supply Actuator exchange is complete 6 3 Safety switch Cleaning Do not use aggressive cleaning agents Do not use substances that interfere...

Page 27: ...ING INST R U CT IO NS MICS3 OS3 electr protection hood Subject to change without notice MAINTENANCE 6 6 4 Spare parts list Designation Type Part number Thomson actuator Actuator with M12 male connect...

Page 28: ...28 8025999 V1 0 2021 02 SICK OP ER A T ING INST R U CT IO NS MICS3 OS3 electr protection hood Subject to change without notice 6 MAINTENANCE...

Page 29: ...applicable local and statutory environmental regulations and guidelines for the dis posal of industrial and electrical waste must be observed Disposal of batteries electrical and electronic devices In...