OPERATION
8.2.6
N/O output with error signal
Application
If there is an error message at the LFP, this can be transferred using a switching contact.
Configuration
1.
Configure the Qx switching output as normally open.
•
Set the parameter in the QxMENU-OUx menu to Qx_Eno.
2. Select the electrical property (NPN/PNP/DRV (push/pull)).
Select the parameter in the QxMENU-TYPx menu.
The following rules apply:
•
Qx-PNP = Switching output in PNP circuit
•
Qx-NPN = Switching output in NPN circuit
•
Qx-Drv = Switching output in push/pull function
8.2.7
N/C output with error signal
Application
If there is an error message at the LFP, this can be transferred using a switching contact.
Configuration
1.
Configure the Qx switching output as normally closed.
•
Set the parameter in the QxMENU-OUx menu to Qx_Enc.
2. Select the electrical property (NPN/PNP/DRV (push/pull)).
Select the parameter in the QxMENU-TYPx menu.
The following rules apply:
•
Qx-PNP = Switching output in PNP circuit
•
Qx-NPN = Switching output in NPN circuit
•
Qx-Drv = Switching output in push/pull function