© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD 29
Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
System integration and configuration
Assembly parameter “Validation”
The following options are available for validation:
Option
Description
No validation
Validation is deactivated. Every IO-Link device is accepted.
Compatibility
(VID + DID)
Vendor ID and device ID are compared with the module
data. IO-Link communication only starts if they match.
Vendor ID and Device ID are input in decimals.
Identity
(VID + DID + SN)
Vendor ID, device ID, and serial number are compared with
the module data. IO-Link communication only starts if they
match. Vendor ID and Device ID are input in “decimals”,
the serial number is input in “visible string”.
Table 14: Validation
Example
Fig. 9: Validation example
• VID = 26 (SICK AG)
• DID = 8388615 (0x800007)
• VID: 0
• VID1: 26
• DID0: 128 (0x28)
• DID1: 0 (0x00)
• DID2: 7 (0x07)