© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD 17
Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
Electrical connection
Functional grounding
Fig. 4: Ground connection
7. IO-Link ports that are not in use must be sealed with M12 blind plugs
to ensure the enclosure rating of IP 67.
NOTE!
Four M12 blind plugs are included in the scope of delivery.
5.3
Connection diagrams
5.3.1
Connection diagram for “POWER IN” and “POWER OUT” supply voltage
1
5
3
4
2
5
1
3
2
4
Fig. 5: Supply voltage
Right: POWER IN 7/8” male connector, 5-pin
Right: POWER OUT 7/8” female connector, 5-pin
Contact
Signal
Description
1
0 V
Actuator supply ground
2
0 V
IO-Link Master and/or sensor supply ground
3
FE
Functional grounding
4
DC 24 V
IO-Link Master and/or sensor supply
5
DC 24 V
Actuator supply
Table 7:
Description of “POWER IN” and “POWER OUT” supply voltage