Operating instructions IO-Link Master IOLG2PN-03208R01 – PROFINET
System integration and configuration
28
© SICK AG • Presence Detection • Subject to change without notice • 8018665.10RD
IO-Link diagnostic settings
The IO-Link diagnosis for the respective port is activated or deactivated via
this module. The diagnosis data can be read out via PLC/fieldbus only if
the diagnosis is set.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Port 7
Port 6
Port 5
Port 4
Port 3
Port 2
Port 1
Port 0
IO-Link communication
Bit status for each IO-Link port, feedback whether a communication is
established.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Port 7
Port 6
Port 5
Port 4
Port 3
Port 2
Port 1
Port 0
Female connector peripheral error
This module indicates whether an error has occurred on a port.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Port 7
Port 6
Port 5
Port 4
Port 3
Port 2
Port 1
Port 0
Short-circuit sensor supply
This module indicates whether there is a short-circuit in the sensor supply
on a port.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Port 7
Port 6
Port 5
Port 4
Port 3
Port 2
Port 1
Port 0
Station diagnostic
This module indicates which error has occurred.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
IO-Link
short-
circuit
Actuator
warning
Actuator
short-
circuit
Sensor
voltage
short-
circuit
External
error
res.
US actu-
ator
US
sensor
Display LED
This module enables you to control the display LEDs.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Green
LED
Red
LED
Assembly parameter
“Cycle settings”
The speed of the IO-Link communication is affected by this parameter. The
IO-Link cycle time is calculated with the variables “Basic cycle time” and
“Multiplier”. The time is selected using the “Basic cycle time” field. Input
between 0 to 63 (decimal) for the “Multiplier”.
Assembly parameter
“Data selection”
These settings only apply to the input data.
Establish the start byte of the process data with the field “Data segment
offset”. Input the actual process data length of the IO-Link device in the
field “Max. input data length”.
Using an IO-Link module with corresponding process data length you can
adapt the visible data window to the input data.