Commissioning and parameterization
4.2.8
Configuring the limit value relay
Select directory “Configuration / Limit Value Switches” for configuring.
Fig. 63
”Configuration / Limit Value Switches” directory
* Not relevant for FLOWSIC200
Field
Parameter
Remark
Source sensor
Sensor 1 to 8
Sensor for which a limit value is to be assigned to the output signal.
Source Value
Measured value 1 Volume flow in operating conditions*
Measured value 2 Flow velocity
Measured value 3 Sound velocity
Measured value 4 Acoustic temperature
Measured value 5 Temperature A*
Measured value 6 Temperature B*
Measured value 7 Signal to noise ratio A
Measured value 8 Signal to noise ratio B
Limit value
Value
The limit value relay switches when the entered value is overflown or underflown.
Switch at
Over Limit
Define the switching direction
Underflow
Hysteresis
type
Percent
Assignment of the value entered in the “Hysteresis type” field as relative or absolute
value of defined limit value
Absolute
Hysteresis
Value
Define a tolerance for resetting the limit value relay
Aim bit at MCU status Relay 5
Aim bit at MCU status = special memory in the MCU for monitoring limit values