- 12 - 

 

4.3.2 Electric 

wiring 

 

  The electric wiring of the blower must be installed by a qualified electrical engineer, as per 

the “electrical equipment technical standards” and the “extension rules.” 

  Confirm the power supply specified on the product nameplate affixed to the side surface of 

the main body and then use the power supply for this blower. Using a power supply other 
than that specified on the nameplate to operate this blower is dangerous and may cause a 
failure. 

  Select an earth leakage breaker or breaker of the power supply appropriate for the current 

at the time of startup. 

  Ground the blower to prevent electric shocks. 

  Also read the Operating Instructions of the electric motor. 

  Install electric wiring to rotate the blower in the correct direction. (For details, see Section 

4.4.) 

 

4.4 Test operation 

 

Before starting up the blower for test operation, make sure to perform the following inspection 
to confirm that the condition is normal. 

  Confirm that materials, bolts, nuts, tools, etc., used in construction works are not left inside 

the duct or casing, or near the intake port/discharge port. 

  Confirm that the blower installed is free from rattling and that all the bolts and nuts are 

tightened without omission. 

  Confirm that the protective parts used in transport have been removed. 

  Confirm that a metallic wire net has been attached with the intake port/discharge port open.

  Check the electric wiring. 

  Confirm that the items above are normal, turn on the switch once, and then turn it off 

(inching) immediately to check for abnormal vibration or contact sound. At the same time, 
visually confirm the rotation direction. (Affix a seal to the main body to indicate the rotation 
direction.) If the blower rotates in the reverse direction, it makes the air flow in the reverse 
direction. 

  If the rotation direction is reversed, turn off the source power supply, switch two of the three 

power cables with each other while the other cable remains connected, and then confirm 
the rotation direction. Since different motor rotation directions and motor installation 
directions are available for the blower, the wiring method may differ from the indication on 
the motor terminal box. Also, since the colors of cables and phase of the power supply may 
differ depending on the power company, reverse rotation may occur even if cables of the 
same color are connected. When the power is initially supplied, make sure to confirm the 
rotation direction. 

  If no abnormality is found during inching, rotate the blower continuously to check for 

abnormal noise. In addition, measure and record vibration values and current values, and 
confirm that they are in the normal ranges. 

  Before starting the formal operation, replenish the blower with the specified grease that 

came with the blower. (See Section 5.2.) 

  When using an air flow adjustment damper, open it fully at first, and then gradually throttle it 

to reduce the degree of opening. If a change is detected in the course of throttling the 
damper, e.g., sudden noise, increase in vibration, decrease in pressure, etc., degree of 
opening to the fully closed side is not allowed so as to prevent stalling. When an axial flow 
type blower is used, the range of air flow adjustment by a damper is limited and a judgment 
must be made taking into account the above-mentioned consideration. It is recommended 
to change the rotation speed for air flow adjustment. 

 
 

Summary of Contents for MAA1050-Y005E

Page 1: ...MAA1050 Y005E Blower Operating Instructions Axial Flow Mixed Flow Type Blower...

Page 2: ...ification of the V belt drive blower blower in which a motor pulley and V belt are incorporated Only the main body of the motor shaft direct coupling blower impeller is an accessory These Operating In...

Page 3: ...stallation 8 4 1 Installation 8 4 2 Duct connection 9 4 3 Installation of the motor when the blower adopts the specification of V belt drive main body only 10 4 4 Test operation 12 5 Operation 13 5 1...

Page 4: ...rush out This may cause a serious accident Keep your face away from around the discharge port Small dust etc taken in by the blower may rush out of the discharge port at a high speed If such dust ente...

Page 5: ...xtension rules Also refer to the Operating Instructions of the motor Before starting test operation confirm that nothing is left in the connected duct or casing or near the intake port discharge port...

Page 6: ...mercial inverter is not suitable for the blower Change the following values at least Base frequency Adjust to the rated frequency of the blower 50 Hz or 60 Hz Highest frequency Adjust to the rated fre...

Page 7: ...table below The model is indicated on the product nameplate nameplate affixed to the side face of the blower main body casing A V 5 K M Blank Main body only M With a motor Blank Motor shaft direct cou...

Page 8: ...n the case of the specification of main body only none of the motor pulley on the motor side and V belt are attached to the blower V belt drive Motor shaft direct coupling Normal temperature specifica...

Page 9: ...manually carefully prevent the hand from being caught 4 Installation 4 1 Installation 4 1 1 Selection of installation location Install the blower in a location as shown below A location at a normal te...

Page 10: ...t resulting in damage to the product When installing the duct pay attention to the following points 1 When using a flexible joint apply appropriate tension to it Keep the length to the minimum necessa...

Page 11: ...ension of the belt use adjustment nuts to fix the motor base Procedure for tensing the belt Step 1 Span calculation First calculate the span of the V belt The span of the V belt is part of the connect...

Page 12: ...range of small diameter of 3V 5V type is indicated in nominal diameter A lack or excess of belt tension causes abnormal phenomena The following table indicates how to distinguish a lack of belt tensi...

Page 13: ...ally confirm the rotation direction Affix a seal to the main body to indicate the rotation direction If the blower rotates in the reverse direction it makes the air flow in the reverse direction If th...

Page 14: ...k the temperature near the bearing and any changes to it Electrical section Check the current value and voltage value and any changes to them Component inspection V belt Check the tension Check for we...

Page 15: ...specified grease Temperature specification of blower Grease manufacturer Product name of grease brand Normal temperature specification Showa Shell Sekiyu K K Albania S3 Heat proof specification Dow Co...

Page 16: ...aring type Repleni shment amount g Bearing type Repleni shment amount g Bearing type Repleni shment amount g Bearing type Replenis hment amount g Bearing type Replenis hment amount g UC203 204 205 206...

Page 17: ...efore the restart of operation make sure to perform an inspection similar to that for test operation In particular check for materials adhering to the impeller or for corrosion on it 6 About the rotar...

Page 18: ...actors such as salt damage and public pollution abnormal voltage use of a power supply voltage or frequency other than that specified or the like Failure or damage due to repair or modification includ...

Page 19: ...Replacement or recycling Inappropriate material Replacement Unbalanced impeller Correction Deformation or damage of impeller Repair or replacement Wear or corrosion of impeller Repair or replacement...

Page 20: ...purchased blower Fan identification information that you may need when making an inquiry of us TYPE SERIAL NO Date of Purchase Year Month Day Date of start of operation Year Month Day Supplier TEL Per...

Reviews: