background image

6

3. Add the Btu/Hr of all fuel burning appliances in the

space.
Vent-free log set _______________ Btu/Hr
Gas water heater* ______________ Btu/Hr
Gas furnace ___________________ Btu/Hr
Vented gas heater ______________ Btu/Hr

Gas fireplace logs

______________ Btu/Hr

Other gas appliances*   + ________ Btu/Hr
Total                              = ________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent

draws combustion air from the outdoors and vents to

the outdoors.

Example:
Vent-free log set ______________ Btu/Hr
Gas water heater* _____________ Btu/Hr
Total                              = ________ Btu/Hr

4. Compare the maximum Btu/Hr the space can support with

the actual amount of Btu/Hr used.

____ Btu/Hr (max. the space can support) 
____ Btu/Hr (actual amt. of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can sup-

port)
73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a

confined

space because

the actual Btu/Hr used is more than the maximum Btu/Hr

the space can support. You must provide additional fresh

air. Your options are as follows:
A. Rework work sheet, adding the space of an adjoining room.

If the extra space provides an

unconfined

space, remove

door to adjoining room or add ventilation grills between

rooms. See Ventilation Air from Inside Building, page 5.

B. Vent room directly to the outdoors. See Ventilation Air

from Outdoors, page 5.

C. Install a lower Btu/Hr appliance, if lower Btu/Hr size

makes room unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr

the space can support, the space is an

unconfined

space.

You will need no additional fresh air ventilation. 

39,000
40,000
79,000

AIR FOR COMBUSTION 

AND VENTILATION

WARNING: If the area in which the

heater may be operated does not meet the

required volume for indoor combustion

air,combustion and ventilation air shall be

provided by one of the methods described

intheNationalFuelGasCode,ANSIZ223.1/

NFPA 54, the International Fuel Gas Code,

or applicable local codes.

CONTINUED

VENTED OPERATION

Area of Various Standard

Round Flues

Diameter (ins.)

Area (sq. ins.)

5"

20 sq. inches

6"

29 sq. inches

7"

39 sq. inches

8"

51 sq. inches

three reasons for operating your heater in the vented mode:

1. The fireplace does not meet the clearance to com-

bustibles requirements for vent-free operation.

2. State or local codes do not permit vent-free operation.

3. You prefer vented operation.

If reasons number 1 or 2 above apply to you, you must per-

manently open chimney flue damper. You must install the

damper clamp. This will insure vented operation (see 

Fig-

 

u re 10).

The damper clamp will keep damper open.

See chart below for minimum permanent flue opening

you must provide. Attach damper clamp so the mini-

mum permanentflue opening will be maintained at all times.

Follow instructions 

Installing  Damper Clamp

 on 

page 8 for location of damper in the fireplace.

Damper

Clamp

Damper

Chimney

Minimum Permanent

Height (ft.) Flue Opening (sq. ins.)

6' to 15'

39 sq. inches

15' to 30'

29 sq. inches

The

Nationa

l

FuelGasCode

,

 A N SI Z223.1/NFPA 54

 defines a confined space as a space

space whose volume is less than 50 ft

3

per 1000btu/hr (4.8 m

3

 per kw) of the aggregate

input of all appliances installed in that space. Rooms communicating directly with the 

space in which the appliances are installed, through openings not furnished with doors 

are considered a part of the unconfined space.

Note: When used as a vented heater, appliance must 

be installed only in a solid-fuel burning fireplace with 

a working flue and constructed of noncombustible 

material.

You may also use this heater as a vented product. Thereare

Summary of Contents for GEORGIA REGAL

Page 1: ...LLER Leave this manual with the appliance CONSUMER Retain this manual for future reference This appliance may be installed in an aftermarket permanently located manu factured mobile home where not prohib ited by local codes This appliance is only for use with the type of gas indicated on the rating plate This app liance is not convertible for use with other gases Aftermarket Completion of sale not...

Page 2: ...replace screen is in place before funning this app liance Unless other provisions are made for comb ustion air the screens shall have an opening or openings for introduction of combustion air into the fireplace If this appliance is installed in a fireplace that has glass doors the doors must be left open when the appliance is in use WARNING This product can expose you to chemicals including lead a...

Page 3: ... system The ODS shuts down the fireplace if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 If appliance keeps shutting off see Troubleshooting pages 17 through 20 11 Do not run appliance where flammable liquids or vapors are used or stored under dusty conditions 12 Do not use this appliance to cook food or burn paper or other objects 13 Never place any ob...

Page 4: ...s no matches batteries or other sources to light heater PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code and Ventilation All spaces in homes fall into one of the following ventilation classifications 1 Unusually Tight Construction 2 Unconfined Space Theinformationonpages4through6willhelpyouclassify your space and provide adequate ventilation WARNING This heater s...

Page 5: ...outlet air into attic if attic has a thermostat controlled power vent Heated air entering the attic will activate the power vent Figure 1 Ventilation Air from Inside Building Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Figure 2 VentilationAir from Outdoors DETERMINING FRESH AIR FLOW FOR APPLIANCE LOCATION Determining if You Have a Confin...

Page 6: ...may be operated does not meet the required volume for indoor combustion air combustion and ventilation air shall be provided by one of the methods described intheNationalFuelGasCode ANSIZ223 1 NFPA 54 the International Fuel Gas Code or applicable local codes CONTINUED VENTED OPERATION Area of Various Standard Round Flues Diameter ins Area sq ins 5 20 sq inches 6 29 sq inches 7 39 sq inches 8 51 sq...

Page 7: ...inyl or cloth wall cover ingsoroperatingappliancewhereimpurities suchastobaccosmoke aromaticcandles cleaning fluids oil or kerosene lamps etc in the air exist may discolor walls IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing appliance in rooms without enough ventilation air may cause mildew to form CHECK GAS TYPE Use the correct gas type natural gas or pro...

Page 8: ...uce incoming gas pressure Youmustreduceincominggaspressuretobetween 11 and 14 of water If you do not reduce incoming gas pressure heater regulator damage could occur Install the external regulator with the vent pointing down as shown in Figure 4 Pointing the vent down protects it from freezing rain or sleet INSTALLATION CLEARANCES WARNING Maintaintheminimumclear ances Mantel Clearances for Install...

Page 9: ...at you install a sediment trap in supply line as shown in Figure 5 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and appliance Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into appliance gas controls If sediment trap is not installed or is instal...

Page 10: ...n gas valve located on or near gas meter of natural gas or by using compressed air 3 Check all joints from gas meter to equipment shutoff valve for natural gas or propane supply to equipment shutoff valve for propane gas Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 4 Correct all leaks at once CONTINUED 10 REMOTE CONTROL SET INSTALLATION AND OPERATION COMMUNICATI...

Page 11: ...ly function is to be decorative Simply spread the Crushed Shale on your fireplace floor around the bottom of your log set burner grate to give the appearance of burnt ash It can also be used to cover your gas supply Caution Never place the shale or any other object not provided with your gas log set and instructed for that purpose onto the burners of the unit Be creative in the placement You do no...

Page 12: ... midway back on grate Log 4 in notches at left Log 5 in notches at right Place log 1 at back Log 6 crossing Log 4 at the top left to Log 1 Center in fireplace Log 3 at front of grate Place Logs 7 and 8 on the Log 1 Log 4 Log 3 Log 2 Log 5 Log 6 Log 7 Log 8 1 2 3 4 5 6 7 8 ...

Page 13: ...NS WARNING If operate this heater with glass doors closed If you operateheaterwith doorsclosed heat buildup inside fireplace willcauseglasstoburst Make suretherearenoobstructions across openings of fireplace You must operate this heater with sure fireplace screen is closed before running heater NOTICE Duringinitialoperationof new heater burning logs will give off a paper burning smell Orange flame wi...

Page 14: ...ton This will light pilot The pilot is attached Note If pilot does not light no spark contact a qual ified service person or gas supplier for repairs Until re with match see Manual Lighting Procedure page 15 8 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas...

Page 15: ... Replace or remove low batteries as soon as possible to prevent corrosion damage to remote control acces sory 15 HAND HELD TRANSMITTER OPERATION Move the side Slide Switch into the ON position tow ards the flat end of the unit Press and hold the control button see Figure 11 on the Hand Held Remote until burner turns on Press and hold the control button again until the burner turns off Figure 11 ON...

Page 16: ...nd let cool Remove blockage Blocked burner flame holes will create soot MAIN BURNER BURNER FLAME PATTERN Figure 15 shows the correct burner flame patern Figure 16 shows the incorrect burner flame patern turn Gas Log Set off see Turning OFF the Ap pliance page 15 see Cleaning and Maintenance this page see Troubleshooting page 22 CLEANING AND MAINTENANCE WARNING Turn off Gas Logs and let CAUTION keep...

Page 17: ... See Fig 18 See Fig 18 Figure 18 Pilot Inlet Air Hole 19 17 ...

Page 18: ...18 ...

Page 19: ...19 ...

Page 20: ...Model Number GRVFE24 N L 1 2 3 4 9 10 11 11 L 14 7 O O 5 0 0 6 0 0 o 8 311 20 24 12 o 13 L 14 15 16 21 17 18 19 22 25 24 23 20 ...

Page 21: ...0 Decorative Rock RMH 120 EBTBR RMH 120 EBTBR Tray Bracket Right 1 1 Tray Bracket Left RMH 120 EBTBL RMH 120 EBTBL RMH 120 00260 RMH 120 00254 RMH 120 18318 RMH 120 08419 NG RMH 120 08421 P RMH 120 90434A SBNCJ00071A SH 111 RMH 120 00051 49738375 Orifice Holder EB Tee 375 Comp Tube 375 EB Elbow Piezo Igniter RMH 120 90945 RMH 120 90945 RMH 120 00546 RMH 120 CMPT RMH 120 CMPT RMH 120 1831805 RMH 12...

Page 22: ... low pilot will not stay lit heater will not produce the specified heat propane gas supply volume may be low You may feel your gas pressure is too low If so contact your local natural or propane gas supplier Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty TECHNICAL SERVICE You may have further questions about installation opera ti...

Page 23: ...NOTES 23 ...

Page 24: ...coloring of any kind use or installation contrary to specified instructions and applicable building codes including heating the product to temperatures above its rated specifications which can cause considerable warping disassembly including removal of the product from a built in installation damage resulting from accident alteration misuse abuse hostile environments or improper installation repair...

Reviews: