44
Character
Name, Function, Setting Range
Default Value
Manual reset value
0.0
• Sets the Manual reset value.
• Available when P (I=0, D=0) or PD (I=0) is the control action.
• Setting range: -100.0 to 100.0
( )
DC current, voltage input: -1000 to 1000 (The placement of the decimal point follows the
selection.)
Proportional cycle
• Sets the proportional cycle.
Relay contact output: 30 sec
Non-contact voltage output: 3 sec
• Not available for ON/OFF control or DC current output type.
• Setting range: 1 to 120 sec
Alarm 1 value
0
• Sets the Alarm 1 value.
• Setting the value to 0 or 0.0 disables the function (except Process high and Process low
alarm).
• Not available if No Alarm action is selected during Alarm type selection.
• Setting range: See (Table 9.2-1) on p.41.
Alarm 2 value
0
• Sets the Alarm 2 value. (Refer to Alarm 1 value.)
Available only when the AO or AW option is added.
Alarm 3 value
0
• Sets the Alarm 3 value. (Refer to Alarm 1 value.)
Available only when the AO option is added.
Alarm 4 value
0
• Sets the Alarm 4 value. (Refer to Alarm 1 value.)
Available only when the AO option is added.
Heater burnout alarm 1 value
0.0 A
and CT3
current,
alternating
display on
the PV/SV
display
• Sets the heater current value for Heater burnout alarm 1 (CT3).
Setting to 0.0 disables the alarm.
CT3 current value and character
are alternately indicated on the PV/SV display.
When the output is ON, the CT3 current value is updated.
When the output is OFF, the WCL-13A memorizes the previous value when the output
was ON.
• It is recommended to set approx. 80 % of the heater current value in consideration of
the voltage fluctuation.
• Available only when Heater burnout alarm (W, W3 option) is added.
• Setting range:
Rated current 20 A: 0.0 to 20.0 A,
100 A: 0.0 to 100.0 A
Heater burnout alarm 2 value
0.0 A
and
CT4 current,
alternating
display on
the PV/SV
display
• Sets the heater current value for Heater burnout alarm 2 (CT4).
Setting to 0.0 disables the alarm.
CT4 current value and characters
are indicated alternately on the PV/SV display.
When the output is ON, the CT4 current value is updated.
When the output is OFF, the WCL-13A memorizes the previous value when the output
was ON.
• It is recommended to set approx. 80 % of the heater current value in consideration of
the voltage fluctuation.
Available only when Heater burnout alarm (W3 option) is added.
• Setting range:
Rated current 20 A: 0.0 to 20.0 A,
100 A: 0.0 to 100.0 A