- 149 -
Characters,
Factory Default
Setting Item, Setting Range
Data
a1hy
/ //1.0
EV1 alarm hysteresis
Setting range: 0.1 to 1000.0
( ),
DC voltage, current inputs: 1 to 10000 (The placement of the
decimal point follows the selection.)
Available when any alarm from
/001
(High limit alarm) to
/012
(High/Low limits
with standby independent alarm) is selected in [Event output EV1 allocation].
a1dy
/ ///0
EV1 alarm delay time
Setting range: 0 to 10000 seconds
Available when any alarm from
/001
(High limit alarm) to
/012
(High/Low limits
with standby independent alarm) is selected in [Event output EV1 allocation].
a1lm
/ noml
EV1 alarm Energized/De-energized
noml
Energized
revs
De-energized
Available when any alarm from
/001
(High limit alarm) to
/012
(High/Low limits
with standby independent alarm) is selected in [Event output EV1 allocation].
evo2
/ /000
Event output EV2 allocation
/000
No event
/001
Alarm output, High limit alarm
/002
Alarm output, Low limit alarm
/003
Alarm output, High/Low limits alarm
/004
Alarm output, High/Low limits independent alarm
/005
Alarm output, High/Low limit range alarm
/006
Alarm output, High/Low limit range independent alarm
/007
Alarm output, Process high alarm
/008
Alarm output, Process low alarm
/009
Alarm output, High limit with standby alarm
/010
Alarm output, Low limit with standby alarm
/011
Alarm output, High/Low limits with standby alarm
/012
Alarm output, High/Low limits with standby independent
alarm
/013
Heater burnout alarm output (When C5W, EIW or W option
is ordered)
/014
Loop break alarm output
/015
Time signal output
/016
Output during AT
/017
Pattern end output
/018
Output by communication command
/019
RUN output
/020
Heating/Cooling control Relay contact output
When
/001
(High limit alarm) to
/012
(High/Low limit with standby
independent alarm) or
/015
(Time signal output) is selected, one output can be
set to one event output.
When
/
013
(Heater burnout alarm output),
/014
(Loop break alarm),
/016
(Output during AT) to
/019
(
RUN output) are selected, each output is common to
multiple event outputs.
Available when the EV2 or EV3(DR) option is ordered.