- 14 -
(1) Operation Check of Earth Leakage Circuit Breaker
Be sure to always check the earth leakage circuit breakers before starting operation
according to the following procedures.
1)
Start the engine.
(Refer to section "8-1. Starting the Engine".)
2)
Set the idle control switch to "HIGH".
3)
Set the ELCB lever to "ON".
4)
Press the ELCB test button.
Operation is normal if the ELCB lever lowers and
turns off at this time.
5)
Push up the ELCB lever to the "ON" position.
There is a fault in the earth leakage circuit breakers if
operation cannot be checked according to the above
procedures. Request repair at the retail outlet where the
equipment was purchased.
(2) Bonnet Grounding Terminal
The equipment includes a bonnet grounding terminal in
order to connect bonnet ground wire.
A neutral point of the AC power source is connected to
the bonnet grounding terminal.
<Note>
Connect using a plug with a grounding pole.
If using a plug without a grounding pole, perform grounding work and check that used
devices are connected to ground.
Securely ground the bonnet grounding terminal to the metal frame of the vehicle if
transporting the equipment by truck or trailer.
(3) If an Earth Leakage Circuit Breaker Operates
Caution:
Electric Shock/Injury
Always be sure to turn off the power switches of all devices using the equipment
when turning on the equipment breakers after an earth leakage circuit breakers
operates. Leaving on the power switch of a device using the equipment when the
equipment breakers are turned on could result in the sudden operation of the
corresponding device.
The ELCB lever moves to "OFF" when earth leakage circuit breakers operate.
When this occurs, immediately stop the engine and repair the earth leakage location.
After repairing all faults, push up the ELCB lever to the "ON" side to reset the system.
5-9. Emergency Stop Switch
Press the emergency stop switch to stop the engine
immediately.
After pressing the emergency stop switch, securely return the
starter switch to the "STOP" position and turn the emergency
stop switch clockwise to reset the switch.
Idle Control
Switch
Test Button
ELCB
Bonnet Grounding
Terminal
Stop
Reset
Summary of Contents for DGW400DMK
Page 2: ......
Page 41: ... 38 15 Engine Wiring Diagram ...
Page 42: ... 39 16 Generator Wiring Diagram P 1 2 ...
Page 43: ... 40 P 2 2 ...
Page 44: ... 41 MEMO ...
Page 45: ... 42 MEMO ...
Page 46: ... 43 MEMO ...
Page 47: ... 44 ...
Page 48: ... 45 2015 ...