41
< Note >
When removing or attaching the plug, hold the drain valve fixed using a spanner or similar tool
and turn the plug.
If oil or other liquid is mixed in with the flushed liquid, this indicates that there is an oil leak. In such
case, check for the leak location.
The types of liquids that can accumulate in the spill containment include oil, fuel, coolant water
and battery fluid such that it is not possible to distinguish between rain water and other liquids.
Dispose of flushed liquids according to the related laws and regulations.
Close the valve lever after the liquid has been flushed, and apply sealant coating to the
plug or wrap it in seal tape.
(11) Spill Containment Cleaning/Inspection
WARNING : INJURY
Do not lift up the unit using tie downs. Use of such could result in the generator falling.
No persons should be under a lifted generator at all time.
CAUTION : INJURY
Always be sure to use lifting hooks when lifting up the generator, and raise it
slowly at a completely vertical angle.
Personnel performing lifting work must wear protective gear such as helmets,
safety shoes and gloves.
Do not move the generator during operation.
Clean
Every 500 hours
Separate the spill containment from this generator to clean and inspect the spill containment.
Spill Containment Separate/Reassemble
Turn the 3way fuel valve lever to the “A” side.
Remove the wiring connector.
Remove the fuel hoses (supply and return sides).
Remove the four spill containment fixing bolts (M16, 4 pieces).
3
Plug
Loosen
Tighten
Fixing
Drain Faucet
Drain Faucet
Drain Faucet
Lever
Close
Open
1
2
3
4
Plug(R1/2
”)
Drain Faucet Lever