23
< Note >
If using a single-phase 120 V (between output terminals U-N and W-N), connect an equivalent
load between U-N and W-N
If using a single-phase three-wire output terminal simultaneously with a receptacle output, make
sure that currents passing through each phase is less than the rated current of this generator.
If using at the three-phase 480 V setting, the output voltage of the single-phase three-wire type is
single-phase 240/120 V, which is the same as the three-phase 240 V setting. Accordingly, care
must be taken to not draw an excessive load as the available power is only one half.
8.
Pre-Operation Inspection
WARNING : INJURY
Always be sure to stop the engine and remove the starter key when
performing inspection or maintenance.
Do not open the check door during operation. Be careful of pinching or
catching of moving parts such as the cooling fan and fan belt.
CAUTION : BURNS
Do not touch the engine and surrounding components immediately after
stopping the engine as they are still extremely hot.
CAUTION : FIRE
Always be sure to wipe up any spilled fuel or oil.
8-1. Checking Engine Oil
To check the engine oil, keep the equipment in leveled position, remove the oil level indicator
and wipe so that no oil remains, and then re-insert the dipstick fully. Prior to starting the engine,
make sure to fill the engine oil through the oil filler until it reaches the MAX line.
< Note >
Wait approximately five
minutes or more after
stopping the engine or adding
oil before checking the oil level
again.
An accurate oil level reading
cannot be obtained if the
generator is not placed in
leveled position.
Do not overfill with oil to avoid
engine damage.
OK
Not
Enough
Too
Much
MIN
MAX
Oil Level
Indicator
〇
×
×
Oil Level
Indicator
Oil Filler