(16) Cleaning the Rear Cover
Check/Clean
Every 500 hours
There is a possibility that the drainage inside the rear cover is hindered by accumulation of dust
and the like in the rear cover.
Remove the SCR check panel and Inspection/Cleaning panel of the rear cover.
Please check the inside of the rear cover and clean it if there is garbage.
Attach the SCR check panel and
Inspection/Cleaning panel.
< Note >
Do not open the SCR Check Panel and the
Inspection/Cleaning Panel while the
engine is running. When cleaning, be sure
to run with the engine stopped.
Please clean after SCR system temperature
drops.
When high-pressure cleaning inside the rear
cover is performed, please make sure that
the wiring connector of the SCR system and
the electronic control device do not come
into direct contact with water. Failure to
observe this precaution will cause
malfunction or malfunction.
CAUTION : BURNS
Do not touch the SCR system and surrounding components immediately after
stopping the engine as they are still extremely hot.
CAUTION : INJURY
Position the generator on a level stable surface so that it cannot slide or move in any
manner.
Before starting operation, always be sure to turn off all switches of equipment being
used and all breakers to OFF.
1
2
3
Inspection/Cleaning Panel
SCR Check
Panel
Wiring Connector
View A
Electronic
Control Device
*Shown with SCR Check Panel
( Rear view )
*Shown with SCR Check Panel.( A )