Chapter 7 Operator Control and Display Panel
52
Shield M10U user manual
46
Bypass Fan Fail
At least one of bypass module Fans Fails
47
Manual Shutdown
The N# Power Module is manually shutdown. The power module shuts down
rectifier and inverter, and there’s on inverter output.
48
Manual Boost Charge
Manually force the Charger work in boost charge mode.
49
Manual Float Charge
Manually force the charger work in float charge mode.
50
UPS Locked
Forbidden to shutdown UPS power module manually.
51
Parallel Cable Error
Parallel cables error. Check:
If one or more parallel cables are disconnected or not connected correctly
If parallel cable round is disconnected
If parallel cable is OK
52
Lost N+X Redundant
Lost N+X Redundant. There is no X redundant powers module in system.
53
EOD Sys Inhibited
System is inhibited to supply after the battery is EOD (end of discharging)
54
Battery Test Fail
Battery Test Fail. Check if UPS is normal and battery voltage is over 90% of float
voltage.
55
Battery Maintenance
Fail
Check
If UPS is normal and not any alarms
If the battery voltage is over 90% of float voltage
If load is over 25%
56
Ambient Over Temp
Ambient temperature is over the limit of UPS. Air conditioners are required to
regulate ambient temperature.
57
REC CAN Fail
Rectifier CAN bus communication is abnormal. Please check if communication
cables are not connected correctly.
58
INV IO CAN Fail
IO signal communication of inverter CAN bus is abnormal. Please check if
communication cables are not connected correctly.
59
INV DATA CAN Fail
DATA communication of inverter CAN bus is abnormal. Please check if
communication cables are not connected correctly.
60
Power Share Fail
The difference of two or more power modules’ output current in system is over
limitation. Please adjust output voltage of power modules and restart UPS.
61
Sync Pulse Fail
Synchronization signal between modules is abnormal. Please check if
communication cables are not connected correctly.
62
Input Volt Detect Fail
Input voltage of N# power module is abnormal.
Please check if the input cables are connected correctly.
Please check if input fuses are broken.
Please check if utility is normal.
63
Battery Volt Detect
Fail
Battery voltage is abnormal.
Please check if batteries are normal.
Please check if battery fuses are broken on input power board.
64
Output Volt Fail
Output voltage is abnormal.
65
Bypass Volt Detect Fail
Bypass voltage is abnormal.
Please check if bypass breaker is closed and is good.
Please check if bypass cables are connected correctly.
66
INV Bridge Fail
Inverter IGBTs are broken and opened.
67
Outlet Temp Error
Outlet temperature of power module is over the limitation.
Please check if fans are abnormal.
Please check if PFC or inverter inductors are abnormal.
Please check if air passage is blocked.
Please check if ambient temperature is too high.
68
Input Curr Unbalance
The difference of input current between every two phases is over 40% of rated
current.
Please check if rectifier’s fuses, diode, IGBT or PFC diodes are broken.
Please check if input voltage is abnormal.
69
DC Bus Over Volt
Voltage of DC bus capacitors is over limitation. UPS shutdown rectifier and
inverter.