background image

 

 

 

  www.shieldglobal.com

 

 

     

DATA SHEET

 

 

 

  Note: Specifications are subject to change without notice   

 

 

Specification 

Operating 
Voltage 

loop 24V (16V~28V) 

Standby 
Current 

0.8mA 

Alarm Current 

5.0mA 

Indicator 

Red.  Flashes  in  polling,  and 
illuminates in alarming 

Alarm 
Temperature   

58

 

Class 

A2R 

Alarm Temp

58

Programming 
Method 

Electronically programming 

Code Range 

one address within 1

242. 

Wiring 

Ingress 
Protection 
Rating 

IP22 

Environment 
Temperature 

-

10

℃~+

50

 

Relative 
Humidity 

95%, non condensing 

Material  of 

Enclosure 

ABS 

Dimensions 

Diameter: 100mm   

Height: 56mm(base) 

Mounting 
Hole Distance 

45mm

75mm 

Weight 

About 120g 

 

 

 

 

 

 

 

 

 

Maintenance   

 

The  detector  should  be  installed  just  before           
commission  and  kept  well  before  installation. 
Corresponding  measures  should  be  taken  for 
dust-proof, damp-proof and corrosion-proof. 

    Dust covers are an effective way to limit the entry 

of  dust  into  smoke  detector  sensing  chambers. 
Therefore,  the  dust  cover should not be removed 
until the building starts to be used. 

 

Clean the detector at least once 1 year to ensure     
normal operation of the system. 

 

If unwanted alarms are often found of the detector 
on  site,  the  sensing  chamber  should  be  cleaned. 
Power must be removed from the detector before 
cleaning. 

 

Before  cleaning  the  detector,  notify  the  proper 
authorities  that  the  system  is  undergoing 
maintenance and will be temporarily out of service. 
Disable 

the 

zone 

or 

system 

undergoing 

maintenance to avoid any unwanted alarms. 

 

The detector should be tested again after cleaning 
and  re-installing.  Notify  the  proper  authorities 
when the system is back in service. 

 

Fire simulation test should be done to the detector 
at least once 6 months. 

Accessories and Tools 

Model 

Name 

Remark 

D-APP 

Hand  held 
programmer 

Order separately 

DZ-03 

Base 

Order separately 

Limited Warranty 

SHIELD

  warrants  that  the  product  will  be  free  of 

charge for repairing or replacing from defects in design, 
materials and workmanship during the warranty period. 
This warranty doesn’t cover any product that is found 
to have been improperly installed or used in any way 
not  in  accordance  with  the  instructions  supplied  with 
the  product.  Anybody, 

including 

the 

agents, 

distributors  or  employees,  is  not  in  the  position  to 
amend  the  contents  of  this  warranty.  Please  contact 
your  local  distributor  for  products  not  covered  by  this 
warranty. 

 

 

 

 

 

 
 

Non-polarized 2-core for loop. 

Polarized  2-core  for  remote 
indicator. 