  www.shieldglobal.com

 

 

     

DATA SHEET

 

 

 

  Note: Specifications are subject to change without notice   

 

                                       

 

Features 

 

Electronically addressed. 

 

Built-in microprocessor stores 14 history data. 

 

Drift  compensation,  adaptable  to  environment 

extensively. 

 

Combined  smoke  and  heat  algorithm  greatly     

improves detector performance. 

 

Self-diagnostic. 

 

Dirty chamber checking. 

 

  Designed  to  comply  with  EN  54-5/EN  54-7 

standards. 

Description 

D-A410  Intelligent  Combination  Heat/Photoelectric 

Smoke Detector integrates photoelectric detection and 

fixed temperature and rate of rise detection technology 

by  combining  smoke  sensor  and  heat  sensor  in 

mechanism and circuitry structure. Just because of the 

combination  of  smoke  detection  and  heat  detection, 

D-A410 detector not only overcomes the disadvantage 

that  detectors  using  common  infrared  scattering 

technology  are  insensitive  to  black  smoke  with  small 

particles, but also can  pick up fire with obvious rise of 

temperature  such  as  alcohol  flame,  thus  extending  its 

application range. 

Connection and Cabling 

Fig. 1 shows the detector bottom and Fig. 2 the base. 

100mm

C

 

Fig.1                                          Fig.2 

   

 

Recommended Cabling 

1.0 mm

or above fire cable for detector loop, laid out 

through  metal  conduit  or  flame-retardant  conduit. 

Subject to local codes. 

Installation 

A fixed installation direction is ensured by the location 

elements  on  the  detector  and  the  base.  Fix  the  base 

with two tapping screws, and then align mark C on the 

detector with A on the base, rotate the detector to align 

mark  C  with  mark  B  (Refer  to  Fig.  1  and  2  for  the 

position of the marks), the detector will be fitted to the 

base. 

Mounting of the detector is shown in Fig. 3. 

Det ect or

Condui t

Back  Box

Base

 

Fig.3 

 
Application 

 

The detector can be electronically addressed by 
D-APP  Hand  Held  Programmer.  Please  refer  to 

D-APP  Hand  Held  Programmer  Installation  and 
Operation Manual 

for details.   

D-A410   

Intelligent Combination     

Heat/Photoelectric Smoke Detector

 

Addressable Fire Alarm System 

There are four terminals with numbers on the base. 

1&3: Loop connection (polarity-insensitive) 

2: Positive terminal of remote indicator 

4: Negative terminal of remote indicator 