SHENZHEN FANHAI SANJIANG ELECTRONICS JB-QBL-QM200 User Manual Download Page 27

Page 24

If

QUERY

is pressed in the monitoring status, the system will enter the selection of types of historical

records for query (including fire alarm, fault and release) and the “Query” indicator will be lit. The first
digit of the lower nixie tube on the display panel (close to the EMERGENCY RELEASE button) refers to
the type. If it displays as

, it means it will query the fire alarm information; if

QUERY

is pressed

again and

is displayed, it means it will query the fault information; if

QUERY

is pressed for the

third time and

is displayed, it means it will query the release information. If

QUERY

is pressed

after that, the system will return to the fire alarm query status and

will be displayed. Press

QUERY TIME

to enter the information display interface of the corresponding type. The lower nixie tube

displays the fault No. (0-999). The content initially displayed refers to the latest information which is the
amount of the information as well. The LED on the display panel indicates corresponding information (air
release, fire alarm or fault). The upper nixie tube displays the time. The content initially displayed is the
specific year in the format of

??

. If

QUERY TIME

is pressed, month/day information in the format

of

? ?

.

? ?

will be displayed. If

QUERY TIME

is pressed again, the hour/minute information in the

format of

??

:

??

will be displayed. If it is pressed for the third time, the code information in the format

of

-

??

-

will be displayed. If it is pressed for the fourth time, the specific year will be displayed again. At

this time, if

QUERY

is pressed and the number displayed by the lower nixie tube is decreased by 1, the

information recorded at earlier time will be displayed.
If

QUERY

is pressed under the alarm status, the system will query the current information and both the

QUERY indicator and the indicator of the queried content will flash. If

QUERY TIME

is pressed, the

upper nixie tube will display the year, month, day and code of the information. If

QUERY

is pressed

again, another piece of information will be displayed.

The meanings of the information codes:
Valve operations: 1. Standby

2. Delay release through the EXTERNAL button

3. Release through the

EMERGENCY RELEASE button on the display panel

4. Release through the probe

Alarms: 5. Manual alarm

6. Standby

7. Alarm of circuit 1. 8. Alarm of circuit 2

Faults: 9. Release fault

10. Input fault

11. Output fault

12. AC fault

13. DC fault

14. agent drop

15. Fault of circuit 1

16. Fault of circuit 2

17. DC lack

18. AC lack

19. MCP fault

20.

Audible/visual alarm fault

21. Sounder fault

Release: 22. Start time of the EMERGENCY RELEASE button on the display panel
23. Start time of compound fire alarm

24. Start time of external manual release

25. Release

confirmation time
Note: The system will record information by type. It can record 2997 items in all, including 999 items of
fire alarm information, fault information and release information. If the number of each type of information
is more than 999, the earliest information will be covered.

QUERY TIME

and

KEY ON/OFF

form the key lock. Besides, if used with the

QUERY

key, it can finish

the information query.

Reset

It is a reset key for system software. After it is pressed, the system will cancel all alarm and fault

indications and initialize all outputs.

SYSTEM TEST

It is for system test. During the system test process, the indicators will be lit one by one;

the figure on the clock nixie tube will change from 1 to 9 and the audible alarm will change from fault
sound to fire alarm sound, release the countdown sound and release alarm sounds in order. See Fig.6.1
for the conditions of various alarm sounds.

 

Fault Sound

 

 

F
Sound

ire Alarm

 

 

 

Release 

Sound

 

Countdown 

Sound 

Mute

Fig.6.1 Schematic Diagram of the Modes of Alarm Sounds

Summary of Contents for JB-QBL-QM200

Page 1: ...1 JB QBL QM200 Fire Alarm Control Panel Agent Releasing Control Panel...

Page 2: ...de of emergency release delay 11 3 1 4 Setup of the delay mode for the EXTERNAL MANUAL RELEASE button 11 3 1 5 Setup of the control mode of the key lock over the EMERGENCY RELEASE button on the displa...

Page 3: ...ase refer to Chapter V Panel Display and Chapter VI Key On Off Warning It is necessary to dismount all electromagnetic valves electric detonators from the devices which are driven by them during syste...

Page 4: ...ifications 1 AC input voltage AC 220V 20 50Hz AC input power 120W DC standby power DC24V 7 0Ah consisting of two fully sealed maintenance free DC12V 7 0Ah storage batteries connected in series 2 Outpu...

Page 5: ...he display panel and displays the start countdown The delay manner of the manual start may also be set by the user through the jumpers on the display panel too 11 It provides an open circuit fault det...

Page 6: ...N OFF Fig 2 1 Installation Holes of the Case The following requirements should be met during installation of the case There must be a space of at least 1m reserved in front of the case There are cable...

Page 7: ...ecessary to have the AC supply voltage accessed with the help of a voltage stabilizer with a power of larger than 300W or else the switching power supply may be damaged The standby batteries if fully...

Page 8: ...ate ground wires The installation and connection of the system should comply with the requirements of national standard Code for the Installation and Acceptance of the Fire Alarm System GB50166 92 Bui...

Page 9: ...he master control board Single fire alarm active output terminal Note in the access mode above that before the fire alarm controller is delivered the black short wire connected to terminal 19 on the m...

Page 10: ...Page 7 Fig 2 7 Wiring Diagram of the Fire Alarm Controller Active Output...

Page 11: ...Page 8 Fig 2 8 Wiring Diagram of the Fire Alarm Controller Partial Passive Output...

Page 12: ...nal input circuit JP16 Not detect the open fault of the Local Manual Auto signal input circuit JP17 Detect the open fault of the signal input circuit of the detector circuit 2 JP18 Not detect the open...

Page 13: ...n fault of the stop signal input circuit Detect the open fault of the stop signal input circuit JP21 Not detect the open fault of the manual release signal input circuit Detect the open fault of the m...

Page 14: ...he emergency release delay The factory default is OFF that is to say the electromagnetic valves will be started after the set delay time is reached All possible settings of the jumper JP5 are given in...

Page 15: ...h means that the EMERGENCY RELEASE button is not controlled by the key lock All possible settings are given in the table below The EMERGENCY RELEASE button on the display panel is controlled by the ke...

Page 16: ...Page 13 Fig 4 1 Terminal Positions...

Page 17: ...ut circuit ground and the output circuit ground The 24V PGND has been connected with the output circuit ground in the control board 4 2 2 Connection modes of input terminals The local input signals in...

Page 18: ...an open circuit fault detection function is selected the jumper JP20 on the master control board should be set to the ON position as shown in Table 3 1 2 and Fig 4 1 and the built in termination resi...

Page 19: ...s in the control board should not be used and a 10K termination resistor should be arranged at the end of the circuit shown in connection mode B 2 A short circuit of the switch suggests a reset status...

Page 20: ...ly The connection modes of passive output circuits are related to the actual use and will not be introduced here Connection modes of the output circuits Connecti on mode Type of load Connection mode A...

Page 21: ...re alarm will be forbidden even if the compound fire alarm is detected by the detectors The EMERGENCY RELEASE button can still work at this time 3 Terminal 3 on the master control board It is for the...

Page 22: ...t on whether the output circuit has a short or open circuit fault detection function When the connection mode with a short or open circuit fault detection function is selected the jumper JP6 on the ma...

Page 23: ...T ZONE 2 RELEASE HORN STROBE FAULT MANUAL AUTO RELEASE DELAY RELEASE START RELEASE CONFIRM PANEL MUTE DISPLAY TEST ALARM BELL RESET DELAY STOP QUERY QUERY TIME KEY ON OFF Fig 5 1 Schematic Diagram of...

Page 24: ...ator light will be lit RELEASE After the system has entered the release status and the electromagnetic valves have been started this indicator light will be lit HORN STROBE FAULT After a short or open...

Page 25: ...M BELL After the alarm bell is started this indicator light will be lit DELAY STOP After the DELAY STOP button is pressed when the system is in the countdown for release the delay process will be stop...

Page 26: ...ted the HORN STROBE START indicator close to this key will be lit ALARM BELLIf this key is pressed after the key lock is unlocked the alarm bell may be started or stopped After the alarm bell is start...

Page 27: ...and both the QUERY indicator and the indicator of the queried content will flash If QUERY TIME is pressed the upper nixie tube will display the year month day and code of the information If QUERY is p...

Page 28: ...in the format of After BWD key S10 is pressed the figure displayed by the nixie tube will increase within the range of 1 60 in a cyclic way 2 If Switching key S12 is pressed again the nixie tube will...

Reviews: