SHENZHEN FANHAI SANJIANG ELECTRONICS JB-QBL-QM200 User Manual Download Page 18

Page 15

4.2.3 Description of the input terminals on the master control board
1.

Terminal 17 on the master control board: I

t is for the input of the MANUAL RELEASE button (for

the +24V short/open circuit switch and the self-locking switch).

1)

Connection mode 2 should be selected for it. When the connection mode A without an open circuit
fault detection function is selected, the jumper JP21 on the master control board should be set to
the ON position as shown in Table 3.1.2 and Fig.4.1, and the built-in termination resistors in the
control board should be used; when connection mode B with an open circuit fault detection function
is selected, the jumper JP21 on the master control board should be set to the OFF position, the
built-in termination resistors in the control board should not be used and a 10K

Ω

termination resistor

should be arranged at the end of the circuit shown in connection mode B.

2)

A short circuit of the switch suggests a manual release signal input and

the necessity of using the

self-locking switch

. In order to strengthen the anti-jamming level, it is necessary to maintain a

short circuit state from the start of delay to release, or else only horn/strobe output, alarm bell output,
single fire alarm output and compound fire alarm output will be available and the electromagnetic
valves will not operate.

2.

Terminal 18 on the master control board: I

t is to access the MANUAL FIRE ALARM button (for

the +24V short/open circuit switch and the self-locking switch;

To connect the terminal MANUAL

FIRE ALARM button 1

).

1)

Connection mode 2 should be selected for it. When the connection mode A without an open circuit
fault detection function is selected, the jumper JP19 on the master control board should be set to
the ON position as shown in Table 3.1.2 and Fig.4.1, and the built-in termination resistors in the
control board should be used; when connection mode B with an open circuit fault detection function
is selected, the jumper JP19 on the master control board should be set to the OFF position, the
built-in termination resistors in the control board should not be used and a 10K

Ω

termination resistor

should be arranged at the end of the circuit shown in connection mode B.

2)

A short circuit of the switch suggests a fire alarm signal input.

3.

Terminal 19 on the master control board: I

t is for the accession of the LOCAL EMERGENCY

STOP button (for the AGND short/open circuit switch and the self-locking switch).

1)

Before the delivery of the fire alarm controller, terminal 19 has been shorted to ground
through a black conductor (the factory default). This black conductor should be dismounted
when the LOCAL EMERGENCY STOP button is accessed.

2)

Connection mode 1 should be selected for it. When connection mode A without an open circuit fault
detection function is selected, the jumper JP20 on the master control board should be set to the ON
position as shown in Table 3.1.2 and Fig.4.1, and the built-in termination resistors in the control
board should be used; when connection mode B with an open circuit fault detection function is
selected, the jumper JP20 on the master control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used and a 10K

Ω

termination resistor should

be arranged at the end of the circuit shown in connection mode B.

3)

A short circuit of the switch suggests a normal status and an open circuit of the switch suggests an
emergency stop signal input and the necessity of forbidding the output of an electromagnetic valve
driving signal.

4.

Terminal 20 on the master control board: I

t is for the accession of the LOCAL MANUAL/AUTO

switch (for the AGND short/open circuit switch and the self-locking switch).

1)

Before the delivery of the fire alarm controller, terminal 20 has been shorted to ground
through a black conductor (the factory default). This black conductor should be dismounted
when the LOCAL MANUAL/AUTO switch is accessed.

2)

Connection mode 1 should be selected for it. When the connection mode A without an open circuit
fault detection function is selected, the jumper JP16 on the master control board should be set to the
ON position as shown in Table 3.1.2 and Fig.4.1, and the built-in termination resistors in the control
board should be used; when connection mode B with an open circuit fault detection function is
selected, the jumper JP16 on the master control board should be set to the OFF position, the built-in
termination resistors in the control board should not be used and a 10K

Ω

termination resistor should

be arranged at the end of the circuit shown in connection mode B.

3)

A short circuit of the switch suggests an automatic signal input and the switching between the auto
mode and the manual mode can be realized at this time through the MANUAL/AUTO button on the
display panel; an open circuit suggests a manual signal input, and the system is in the manual mode
at this time, switching through the MANUAL/AUTO button on the display panel cannot be realized
and external manual operation is preferred.

4)

Generally speaking, only a LOCAL MANUAL/AUTO switch is connected to terminal 20 on the
master control board for setting the manual/auto mode of the system. However, on some special
occasions where it is necessary to connect multiple LOCAL MANUAL/AUTO switches, either of the
following two methods may be used.

a.

Make all LOCAL MANUAL/AUTO switches connected in parallel. When any of the LOCAL
MANUAL/AUTO switches are in a short-circuit condition, the system will enter the auto mode;
when all of them are in an open-circuit condition, the system will enter the manual mode.

b.

Make all LOCAL MANUAL/AUTO switches connected in series. When any of the LOCAL

Summary of Contents for JB-QBL-QM200

Page 1: ...1 JB QBL QM200 Fire Alarm Control Panel Agent Releasing Control Panel...

Page 2: ...de of emergency release delay 11 3 1 4 Setup of the delay mode for the EXTERNAL MANUAL RELEASE button 11 3 1 5 Setup of the control mode of the key lock over the EMERGENCY RELEASE button on the displa...

Page 3: ...ase refer to Chapter V Panel Display and Chapter VI Key On Off Warning It is necessary to dismount all electromagnetic valves electric detonators from the devices which are driven by them during syste...

Page 4: ...ifications 1 AC input voltage AC 220V 20 50Hz AC input power 120W DC standby power DC24V 7 0Ah consisting of two fully sealed maintenance free DC12V 7 0Ah storage batteries connected in series 2 Outpu...

Page 5: ...he display panel and displays the start countdown The delay manner of the manual start may also be set by the user through the jumpers on the display panel too 11 It provides an open circuit fault det...

Page 6: ...N OFF Fig 2 1 Installation Holes of the Case The following requirements should be met during installation of the case There must be a space of at least 1m reserved in front of the case There are cable...

Page 7: ...ecessary to have the AC supply voltage accessed with the help of a voltage stabilizer with a power of larger than 300W or else the switching power supply may be damaged The standby batteries if fully...

Page 8: ...ate ground wires The installation and connection of the system should comply with the requirements of national standard Code for the Installation and Acceptance of the Fire Alarm System GB50166 92 Bui...

Page 9: ...he master control board Single fire alarm active output terminal Note in the access mode above that before the fire alarm controller is delivered the black short wire connected to terminal 19 on the m...

Page 10: ...Page 7 Fig 2 7 Wiring Diagram of the Fire Alarm Controller Active Output...

Page 11: ...Page 8 Fig 2 8 Wiring Diagram of the Fire Alarm Controller Partial Passive Output...

Page 12: ...nal input circuit JP16 Not detect the open fault of the Local Manual Auto signal input circuit JP17 Detect the open fault of the signal input circuit of the detector circuit 2 JP18 Not detect the open...

Page 13: ...n fault of the stop signal input circuit Detect the open fault of the stop signal input circuit JP21 Not detect the open fault of the manual release signal input circuit Detect the open fault of the m...

Page 14: ...he emergency release delay The factory default is OFF that is to say the electromagnetic valves will be started after the set delay time is reached All possible settings of the jumper JP5 are given in...

Page 15: ...h means that the EMERGENCY RELEASE button is not controlled by the key lock All possible settings are given in the table below The EMERGENCY RELEASE button on the display panel is controlled by the ke...

Page 16: ...Page 13 Fig 4 1 Terminal Positions...

Page 17: ...ut circuit ground and the output circuit ground The 24V PGND has been connected with the output circuit ground in the control board 4 2 2 Connection modes of input terminals The local input signals in...

Page 18: ...an open circuit fault detection function is selected the jumper JP20 on the master control board should be set to the ON position as shown in Table 3 1 2 and Fig 4 1 and the built in termination resi...

Page 19: ...s in the control board should not be used and a 10K termination resistor should be arranged at the end of the circuit shown in connection mode B 2 A short circuit of the switch suggests a reset status...

Page 20: ...ly The connection modes of passive output circuits are related to the actual use and will not be introduced here Connection modes of the output circuits Connecti on mode Type of load Connection mode A...

Page 21: ...re alarm will be forbidden even if the compound fire alarm is detected by the detectors The EMERGENCY RELEASE button can still work at this time 3 Terminal 3 on the master control board It is for the...

Page 22: ...t on whether the output circuit has a short or open circuit fault detection function When the connection mode with a short or open circuit fault detection function is selected the jumper JP6 on the ma...

Page 23: ...T ZONE 2 RELEASE HORN STROBE FAULT MANUAL AUTO RELEASE DELAY RELEASE START RELEASE CONFIRM PANEL MUTE DISPLAY TEST ALARM BELL RESET DELAY STOP QUERY QUERY TIME KEY ON OFF Fig 5 1 Schematic Diagram of...

Page 24: ...ator light will be lit RELEASE After the system has entered the release status and the electromagnetic valves have been started this indicator light will be lit HORN STROBE FAULT After a short or open...

Page 25: ...M BELL After the alarm bell is started this indicator light will be lit DELAY STOP After the DELAY STOP button is pressed when the system is in the countdown for release the delay process will be stop...

Page 26: ...ted the HORN STROBE START indicator close to this key will be lit ALARM BELLIf this key is pressed after the key lock is unlocked the alarm bell may be started or stopped After the alarm bell is start...

Page 27: ...and both the QUERY indicator and the indicator of the queried content will flash If QUERY TIME is pressed the upper nixie tube will display the year month day and code of the information If QUERY is p...

Page 28: ...in the format of After BWD key S10 is pressed the figure displayed by the nixie tube will increase within the range of 1 60 in a cyclic way 2 If Switching key S12 is pressed again the nixie tube will...

Reviews: