Page 10
Type
Mark
number
Connection
location
Description
JP7
Not detect the short or open fault of the electromagnetic valve output circuit.
Detect the short or open fault of the electromagnetic valve output circuit.
Jumpers
for the
fault
detection
of the input
circuits
JP12
Not detect the open fault of the agent drop alarm signal input circuit.
Detect the open fault of the agent drop alarm signal input circuit.
JP13
Not detect the open fault of the signal input circuit of the detector circuit 1.
Detect the open fault of the signal input circuit of the detector circuit 1.
JP14
Not detect the open fault of the RESET button signal input circuit.
Detect the open fault of the RESET button signal input circuit.
JP15
Not detect the open fault of the Release Confirm signal input circuit.
Detect the open fault of the Release Confirm signal input circuit.
JP16
Not detect the open fault of the Local Manual/Auto signal input circuit.
Detect the open fault of the Local Manual/Auto signal input circuit.
JP17
Not detect the open fault of the signal input circuit of the detector circuit 2.
Detect the open fault of the signal input circuit of the detector circuit 2.
JP18
Not detect the open fault of the MUTE button signal input circuit.
Detect the open fault of the MUTE button signal input circuit.
JP19
Not detect the open fault of the signal input circuit of the manual fire alarm.
Detect the open fault of the signal input circuit of the manual fire alarm.
JP20
Not detect the open fault of the stop signal input circuit.
Detect the open fault of the stop signal input circuit.
JP21
Not detect the open fault of the manual release signal input circuit.
Detect the open fault of the manual release signal input circuit.
Jumpers
for active
output
selection
JP8
Shorting
Set the compound fire alarm output to be active.
Off
Set the compound fire alarm output to be passive.
JP9
Shorting
Set the single fire alarm output to be active.
Off
Set the single fire alarm output to be passive.
JP10
Shorting
Set the fault output to be active.
Off
Set the fault output to be passive.
Output
terminal
J1
Shorting of
terminals
12 and 13
The manual/auto output is active.
Shorting of
terminals
12 and 13
The manual/auto output is passive.
Table 3.1.2 All Possible Settings of the Jumpers on the Master Control Board
Note: When the jumpers are in the ON position, the 10K termination resistors are internally connected
and the short or open circuit faults of the external circuits are not detected; when they are in the OFF
position, namely when the short or open faults of corresponding output circuits are detected, the
detection can be finished by arranging auxiliary circuits at the terminals of corresponding output circuits.
For the use of auxiliary circuits, please see the contents on the connection modes of the output circuits
with a short or open circuit fault detection function in 4.3.1 and 4.3.2 in Chapter IV.
3.1.2 Setup of the start-up delay time of electromagnetic valves
The automatic start-up delay time of the electromagnetic valves of JB-QBL-QM200 is set through the
jumpers JP6, JP7 and JP8 on the display panel as shown in Fig.3.1.2.
And its factory default is 20s.