Pr.035
Setting for output analogy
frequency/current/voltage signal
d0000: Analog frequency meter
( 0 to Maximum Frequency )
d0000
d0001: Analog current meter ( 0 to
250% is associated with output
current )
d0002: Analog voltage meter ( 0 to
250% is associated with output
voltage )
Pr.036
Reserved
d000.1-d600.0s
d000.4
Pr.037
Analog output gain setting
d0001-d200
%
d0100
Pr.038
Reserved
d0000-d0001
d0000
Pr.039
Random frequency setting
d000.0—d0120.0 Hz
d0120.0
Pr.040
Set the delay time of relay
d000.0—d999.9S(when
pr.040=0,the relay close.)
d000.0
Pr.041
Selection the max. voltage for analogy
frequency input
d00.00—d10.00
V
(it’s
whenPr.000=1)
d10.00
Pr.042
Selection the min. voltage for analogy
frequency input
d00.00—d10.00
V(
it’s
whenPr.000=1
)
d00.00
Pr.043
Set the rated speed for motor
d0000—d3000
d1500
Pr.044
Set the rated current for motor
d0030—d0120
%
d0100
Pr.045
Set the no load current for motor
d0000—d0099
%
d0040
Pr.046
Torque compensation setting
d0000—d0010
d0000
Pr.047
Set the torque gain at accelerating
(whenPr.011=0)
d0010—d0200
%
d0100
Pr.048
Set the torque gain decelerating ((whenPr.011=0)
d0010—d0200
%
d0100
Pr.049
Set the output mode for multi-functional
relay
d0000
:
get power at faulty,
otherwise loss power
d0001
:
get power at
running ,otherwise loss power
d0002
:
get power at specified
frequency ,otherwise loss power
d0003
:
get power at random
frequency, otherwise loss power
d0004
:
get power at specified
counter, otherwise loss power
d0005
:
low voltage attained
d0006
:
over voltage attained
d0007
:
over current attained
d0008
:
non-zero speed attained
d0009
:
DC current braking
attained
d0010
:
over torque attained
d0011: external failure attained
d0012: FWD attained
d0013: REV attained
d0000