Pr.023
Setting the
starting
frequency for
the DC current
braking when
shut down motor
Before decelerating to stop,
this parameter is the starting
frequency for DC current
brake. It will work when the
parameter is smaller than
the min. frequency(pr.008)
d000.0—d060.0 Hz
d001.0
Pr.024
Momentary power
loss protection
d0000: Operation stops after
momentary power
Loss.
d0000
d0001: Operation continues after
momentary
power loss. Track down with
operating frequency
d0002: Operation continues after
momentary
power loss. Track up from
minimum output frequency.
d003: refer to Pr025
Pr.025
Setting for restarting time after momentary
power loss
d000.3—d005.0 s
d000.2
Pr.026
Setting for the Max. tracking time when
power on
d000.3—d005.0 s
d000.5
Pr.027
Selection of the max. current for speed
tracking
d0030 —d0200
%
d0150
Pr.028
Selection of the max. input analogy
frequency
d000.0—d120.0
Hz
(when
Pr.000=1)
d050.0
Pr.029
Selection of the min.
input analogy
frequency
d000.0—d120.0
Hz
(when
Pr.000=1)
d000.0
Pr.030
External control terminal setting
(2-wire / 3-wire operation control selection
)
d0000:X5 FWD / STOP, X6 REV /
STOP
d0000
d0001:X5 FWD / REV, X6 RUN /
STOP
d0002: X4,X5,X6 is the 3-WIRE
operation control mode
d0003
:
Shutdown , Closing X5
will FWD motor instantly; During
running, closing X5 will shut down
motor instantly .
Shutdown, closing X6 will REV
motor instantly ; During running,
closing X6 will shut down motor
instantly