Shenbao SBR-26.0H-B-S Installation And Instruction Manual Download Page 13

                                                   Protection

Refrigerant anti-freezing protection(Not available for the moment)

Refrigerant leakage protection(Not available for the moment)

Refrigerant low pressure protection

Gas compressing side high temperature protection

Compressor over-current protection

Refrigerant high pressure protection

System refrigerant inlet pipe sensor protection(Not available for the moment)

System refrigerant outlet pipe sensor protection(Not available for the moment)

Gas compressing side temperature sensor protection

Power source phase protection

Error code

1

2

3

4

5

6

7

8

9

EE

Description for protection function :

1. Refrigerant anti-freezing protection(Not available for the moment)
2. Refrigerant leakage protection(Not available for the moment)
3. Refrigerant low pressure protection:
    After compressor start 3 minutes later,system continuously detect 10 seconds for the low pressure
    switch, if the low pressure switch is opened, system enter to low pressure protection ( error code 3) ,
    when detected low pressure switch is closed, system exit the low pressure  protection  .
4. Gas compressing side high temperature protection :
    After compressor start 5 minutes later, system continuously detect 5 seconds for gas conpressing 
    side, if gas compressing side temperature T3 

120

°

C, system enter to gas compressing side air 

    exhausting  high temperature protection( error code 4) , when detected gas compressing side air
    exhausting tempertaure T3

90

°

C , system exit the gas compressor side high temperature

    protection.
    Remark 1 : P1, P2, P4 protection only  valid when relevant system compressor is on,  If relevant 
   system compressor is off, even the temperature point is reached, protection is not valid. The on 
   or off of the compressor  is detected by compressor current ( 0 or not)
5. Compressor over-current protection:
    System continuously detect 3 seconds for compressor phase 1 (or 2) , If phase 1 (or 2) current 

 1 ,

    system enter to compressor over-current protection( error code 5). When detected  compressor 
    phase 1 (or 2) current 

 1 , system exit the protection of compressor over-current.

6.Gas compressing side high temperature protection:
   When system continuously detects 10 seconds for the relevant system high pressure switch, and
    if high pressure switch is opened , system enter to high pressure protection( error code: 6) when 
   detected the high pressure switch closed, system exit the protection of high pressure.
7. System refrigerant inlet pipe sensor protection(Not available for the moment)
8. System refrigerant outlet pipe sensor protection(Not available for the moment)
9. Gas compressing side temperature sensor protection
    When system continuously detect 5 seconds for the relevant system compressor air exhaust 
    temperature sensor  to be short cuted or opened, system enter to gas compressing side 
    temperature sensor protection (error code 9 ),otherwise system exit the protection .(sensor open 
    or not is detected only after relevant compressor run 1 minutes later)
10. Power source phase protection ( Not valide durning heat pump running)
      Within 10 seconds after heat pump is connected to power source, system detect continuously 2 
      seconds for the system phase , if wrong phase or lack phase, system enter to power source 
      phase protection (error code EE). When this protection is activated,system can not return to
      normal unless re-connecting to power source.
     Remark 2 : system high pressure protection E6, low pressure protection E3, over-current 
     protection E5, gas compressor side air exhausting protection E4 , all are serious system 
     malfunction , if any system appear continuously 3 times for such serious malfunction within 30 
     minutes, system can not return to normal unless re-connecting to power source . During defrosting 
     period, system high/low pressure protection is not valid.

10

SWIMMING POOL HEAT PUMP

Summary of Contents for SBR-26.0H-B-S

Page 1: ...SWIMMING POOL HEAT PUMP UNIT Installation Instruction Manual English Version...

Page 2: ...controller operation guide 3 4 Maintenance 7 5 Malfunction and solution 7 6 Wiring diagram 9 Service 1 How to Obtain Service 11 Attachment 1 The charts displayed for outdoor pool indoor pool 11 2 The...

Page 3: ...e way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision 2 Children should be supervised to...

Page 4: ...ht Gross Weight Unit Dimension L W H Weight kg 15 40 8 30 380 3 50 Scroll Kpa RPM dB A inch 3 m h mm mm W V PH Hz W W W W A A W W BTU h W BTU h W 1 Performance data of Swimming Pool for A type Measure...

Page 5: ...2 SWIMMING POOLHEAT PUMP 2 The dimension for Swimming Pool Heat Pump 710 686 750 1450 1060 SBR 26 0H B S SBR 50 0H A S 760 440 425 470 1115 1250 80 370...

Page 6: ...ler 0 with cooling mode only water heater 3 with heating mode only water cooler and heater 1 and electric heater 2 with auto cooling heating 3 modes button and button Up and down button Integrating wi...

Page 7: ...n Actual tested value Parameter checking and Setting You may enter parameter checking state from any other states by pressing once In the state of Parameter Checking each press on can check the next d...

Page 8: ...n temp for defrosting Temperature of exit defrost under heating model Time of exit defrost under heating model System quantity Automatic restarting Model cooling only heating or cooling auxiliary elec...

Page 9: ...the ON OFF state Keyboard Lock Unlock In default state long press and for 3 seconds AT THE SAME TIME vibrator bee once the keyboard will be locked In the state of Locked long press and for 3seconds v...

Page 10: ...pressure Wrong connections or lack of connection Water flow volume not enough water pressure difference is too low EE 04 EE 05 EE06 EE 08 Defrost code display Wire controller and The PCB connection f...

Page 11: ...220VAC no use 7 COMP1 Compressor of system1 220VAC 8 AC L Live wire 9 AC N neutral wire 10 KYOUT GND On Off switch output no use 11 kDOUT GND Mode output no use 12 NET GND 12V Wire controller 13 KYIN...

Page 12: ...25 BL 26 BL 27 BL 25 BL 26 Y G 27 BRN X9 X10 N T S R System Protection PCB COMP1 VAL1 Switch for streem N T S R S Current checking Current checking 12V GND SYS GND LOW1 LP PUMP BLU BLU t t t t TEMP SE...

Page 13: ...tion System continuously detect 3 seconds for compressor phase 1 or 2 If phase 1 or 2 current 1 system enter to compressor over current protection error code 5 When detected compressor phase 1 or 2 cu...

Page 14: ...nately freon leaks are very uncommon and usually are due to shipping reon If your customer is having a problem and you as the installing dealer have verified that the cause is NOT external to my compa...

Page 15: ...at night Space temperature at night Space humidity at night Some of the charts are Pool Temperature operating period 35 30 25 20 15 10 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Maxlmum Minlmum P...

Page 16: ...unit Space Temperature operating period 40 35 30 25 20 15 10 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Jun Space Temperature Maxlmum Minlmum Maxlmum Minlmum 13 SWIMMING POOLHEAT PUMP Heat pump Outle...

Page 17: ...t Heat Pump Chlorinator 14 SWIMMING POOLHEAT PUMP Pressure type Chlorinator or Brominator In line Chlorinator or Brominator P trap Check valve Water Pump Filter Chlorinator P trap Check valve Water Pu...

Page 18: ...Please use outside water flow switch for backup if inside one is damaged COM GND VCC T1 T2 T3 SW1 SW2 SW3 T4 15 SWIMMING POOLHEAT PUMP...

Page 19: ...8 bushels 2 91 hectolitres American dry 1 pint 33 60 cu in 0 550 litre 1 quart 2 pints 1 101 litres 1 peck 8 quarts 8 81 litres 1 bushel 4 pecks 35 3 litres American liquid 1 pint 16 fluid oz 28 88 cu...

Page 20: ......

Reviews: