INSTALLATIEHANDLEIDING – P13
VERSION 0129NM02INT01
MANUEL D’INSTALLATION – P13 |
P13
EN
NL
FR
DE
091NM20INT04
Wiring advice*
Power cable size
Earthing advice*
Required nominal
input voltage at
charge point
MCB
RCD
Ethernet connection
cable requirements
Ø 10mm - Ø 22,5mm
10mm2 solid wire
6mm2 stranded wire with end ferrules
PE-cable (PEN conductor is not allowed)
Separately installed grounding electrode
< 100 Ohm spreading resistance
230V +/-10% 50Hz
400V (3 x 230V+N) +/-10% 50Hz
Cable grommets sizes
Maximum cable terminal block
TN-system
TT-system
Single phase**
Triple phase**
4. INSTALLATION DETAILS
The electrician is responsible for selecting a cable thickness & safety components appropriate
for the specific situation and according to regulations;
* The electrician is always responsible for selecting a cable thickness appropriate for the specific
situation and according to regulations
** 3-phase charge point can also be connected to 1-phase. In this case the charge point can only
charge on 1-phase
*** The electrician must select a suitable MCB to match the amperage setting of the charge point,
taking into account MCB manufacturer specifications
NOTE:
The charge point can be set between 10A and 16A / 32A (depending on version)
- Wire for the maximum hardware amperage under continuous load
- Calculate with a COS-Phi of 0.8
- Calculate with a max allowable voltage drop over the cable of 2%
- Use shielded cable for underground wiring
C-characteristic***
30 mA Type A (HI, HPI, SI, KV), or 30 mA type B
Standard CAT5 or CAT6 Ethernet cable (UTP cable with RJ45 connectors)