Check of the indoor unit level
After the indoor unit is installed, be sure to check the level of the whole unit. The unit must be placed
horizontally, but the condensate pipe shall be installed obliquely, so as to facilitate the drainage of
condensate.
Installation of rectangular air pipe
Cautions:
• The air supply pipe, and the air intake pipe must be covered with a layer of thermal insulation, so as to avoid
thermal leakage and condensation. Firstly apply liquid nail on the pipes, then attach the thermal insulation
cotton with a layer of tinfoil. Use the liquid nail cover to fix it. Lastly use tinfoil adhesive tape to carefully seal
the joints; other good thermal insulation materials can also be used.
• The air supply pipes and the air intake pipes shall be fixed to the prefabricated boards of the ceiling by using
iron supports. The joints of the pipes must be sealed by glue so as to avoid leakage.
• The design and installation of air pipes must be in conformity with the relevant state engineering criteria.
• The edge of the air intake pipe must be at least 50mm away from the wall. The air intake must be covered
with filter.
• Silencing and shock absorption shall be considered in the design and installation of the air pipes. Additionally,
the noise source must be far away from where people stay. The air intake shall not be located above the
place where users stay (offices and rest places, etc.).
Level gauge
Condensate
Drainpipe
Air Intake
Air Supply
Enlarged View
Condensate Drainpipe
As the inside of the unit is in the
negative pressure status, it is
required to set up a backwater elbow.
The requirements is:
A=B≥P/10+20(mm)
P is the absolute pressure inside the
unit. The unit of the pressure is Pa.
Air Intake
Air Intake
Air Supply
Air Supply
Ceiling Mount
2
3
4
5
6
7
No. Name
Hanger
Air Intake Pipe
Canvas Air Pipe
Air Intake
Filter
Main Air Supply Pipe
Air Supply Outlet