16
AH-S22AW2
AH-S25AW2
1-11
Compressor relay RY1
(1) It is ON during operation, and when operation is
stopped, goes OFF after a delay of 150 seconds
(not immediately).
(2) The minimum OFF time of the relay is 30 seconds.
It will not go ON again before 30 seconds elapses.
ON
OFF
OFF
Air conditioner
operation
Compressor
relay
150 sec.
ON
(3) If air conditioner operation is turned on again
during the 150 second delay before the
compressor relay goes off, the compressor relay
will stay on.
ON
ON
OFF
ON
OFF
Air conditioner
operation
Compressor
relay
150 sec. 30 sec.
ON
ON
OFF
ON
ON
Air conditioner
operation
Compressor
relay
150 sec.
1-12
Auto Restart
When power failure occures, after power is
recovered, the unit will automatically restart in the
same setting which were active before the power
failure.
Operating mode (Cool, Dry)
Temperature adjustment (within 22˚C range)
automatic operation
Temperature setting
Fan setting
Air flow direction
Power ON/OFF
Automatic operation mode setting
Swing louver
Setting not memorized
Timer setting
Full power setting