Problem
Potential cause(s)
Remedies
Fixture operates irregularly / abnormal.
(continued)
Corrupted DMX cable.
Replace or repair defective cables and/or connections.
The fixture operates an internal program.
Go to MENU
→
MANUAL
→
STOP PROGRAM
A corrupted fixture generates noise/disruptions on the
DMX link.
Track and isolate the corrupted fixture.
Power is turned off, fixture keeps running.
The fixture will continue to operate on battery power
after removing the AC power supply if configured so.
See “AC POWER LOSS FUNCTION” in the “Control
menu” on page
To turn off the fixture press and hold ‘ESC’ until the
fixture turns off, or go to MENU
→
POWER OFF.
When operating on battery power, a symbol indicating
the current battery level will be shown in the display.
The fixture suddenly switched to static white
light at full output.
The fixture is configured to emergency light mode.
See “AC POWER LOSS FUNCTION” in the “Control
menu” on page
Configure the AC power loss function according to the
requirements.
The fixture turned off when AC power was
disconnected.
The fixture is configured to power off.
See “AC POWER LOSS FUNCTION” in the “Control
menu” on page