Page 30 of 32
PTU50-51-56 -
advanced confi guration
9.8.3 - LANGUAGE
Position the cursor on LANGUAGE, press ENTER to access.
Sets the menu language: English, Italian, French
Press SCROLL to select the menu language.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
9.8.4 - FREQUENCY
Position the cursor on FREQUENCY, press ENTER to access.
It’s possible to check the computed sensor emission frequency.
LEFT ARROW to exit
9.8.5 - F_ WINDOWS
Position the cursor on F_WINDOWS, press ENTER to access.
It is the increase value (in cm), step to step, of the window width during the
echo signal research phase.
The “F_WINDOWS” is the area where the echo reception is active.
Normally it is positioned around the real echo signal and all echoes
detected within the F_WINDOW are deemed valid.
Example: F_WINDOW parameter set to 5.
- The METER detects an echo signal which is 4 meters from the sensor.
- Suddenly, the echo signal disappears and a new echo signal to 3.5 mt
away from the sensor is detected.
- Each time the echo signal will be emitted, the METER will enlarge
“F_WINDOW” with 5cm step, until covering the new eco detected area.
Now the F_WINDOW will start to tighten around the new echo signal and
the new measurement of 3,5mt distance will be used to calculate the level
measurement, alarm thresholds, etc..
F_WINDOW serves to fi lter false echo signals products, for example, by
the agitator blades
Range: 05÷20
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confi rm.
LEFT ARROW to exit without changes
Default value: 05
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
Ź
ENGLISH
ITALIANO
FRANCAIS
Ź
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
Ź
00.0 kHz
FREQUENCY
OUTPUT SAFE MODE
SET UID
LANGUAGE
FREQUENCY
F_WINDOW
RESTORE SETTING
Ź
05
SET WIDTH