Page 33 of 36
www.sgm-lektra.eu
FLOWMETER -
configuration
8.8.3 - LANGUAGE
Position the cursor on LANGUAGE, press ENTER to access.
Sets the menu language: English, Italian, French
Press SCROLL to select the menu language.
Press ENTER to confirm.
LEFT ARROW to exit without changes
OUTPUT SAVE MODE
SET UID
LANGUAGE
OUTPUT SIMULATION
F. WINDOW
RESTORE SETTING
►
ENGLISH
ITALIANO
FRANCAIS
►
8.8.4 - OUTPUT SIMULATION
WARNING - entering in the SIMULATION function, the current output is not
in function of the level measurement. To restore the current as a measured
level function, press the LEFT ARROW button 3 times (RUN mode)
Position the cursor on OUTPUT SIMULATION, press ENTER to access.
It’s possible to force the analog output to a desired value, from 3,5 to 21mA.
Use UP ARROW and SCROLL to modify the value.
LEFT ARROW to return to the previous menu.
OUTPUT SAVE MODE
SET UID
LANGUAGE
OUTPUT SIMULATION
F. WINDOW
RESTORE SETTING
►
00.0 mA
OUTPUT SIMULATION
8.8.5 - F_ WINDOWS
Position the cursor on F_WINDOWS, press ENTER to access.
It is the increase value (in cm), step to step, of the window width during the
echo signal research phase.
The “F_WINDOWS” is the area where the echo reception is active.
Normally it is positioned around the real echo signal and all echoes detected
within the F_WINDOW are deemed valid.
Example: F_WINDOW parameter set to 5.
- The FLOWMETER detects an echo signal which is 4 meters from the sensor.
- Suddenly, the echo signal disappears and a new echo signal to 3.5 mt
away from the sensor is detected.
- Each time the echo signal will be emitted, the FLOWMETER will enlarge
“F_WINDOW” with 5cm step, until covering the new eco detected area.
Now the F_WINDOW will start to tighten around the new echo signal and
the new measurement of 3,5mt distance will be used to calculate the level
measurement, alarm thresholds, etc..
F_WINDOW serves to filter false echo signals products, for example,
by the agitator blades.
Range: 05÷20
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confirm.
LEFT ARROW to exit without changes
Default value: 05
OUTPUT SAVE MODE
SET UID
LANGUAGE
OUTPUT SIMULATION
F. WINDOW
RESTORE SETTING
►
05
F_WINDOW