Page 15 of 36
www.sgm-lektra.eu
FLOWMETER -
configuration
8.2.1 - RELAY
Position the cursor on RELAY, press ENTER to confirm
In this sub-menu it’s possible to setup the on-board relays
RL1 can be set as volume pulse output relay;
RL2 can be set as instantaneous flow rate threshold relay or diagnostic relay.
Press SCROLL button to select the operation mode,
then pressing ENTER to confirm the selection
RELAYS
SET MAX FLOW
FILTER COEFFICIENT
BLIND DISTANCE
►
RL1 COUNTER
RL2 THRESHOLD
RL2 DIAGNOSTIC
►
8.2.2 - RL1 COUNTER
Position the cursor on RL1 COUNTER, press ENTER to confirm
Set the single pulse value, in m3
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: 0
00000.00
RL1 COUNTER
m³
RL1 COUNTER
RL2 THRESHOLD
RL2 DIAGNOSTIC
►
8.2.3 - RL2 THRESHOLD
Position the cursor on RL2 THRESHOLD, press ENTER to confirm
In this submenu you can set the set-point and the RL2 action type.
Press SCROLL button to select the parameter to be programmed.
Press ENTER to confirm.
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►
RL1 COUNTER
RL2 THRESHOLD
RL2 DIAGNOSTIC
►
8.2.3.1 - VALUE
Position the cursor on VALUE, press ENTER to confirm
It’s possible to input the flow rate threshold value in m3/h.
Use UP ARROW and SCROLL to modify the value.
Press ENTER to confirm. LEFT ARROW to exit without changes
Default value: 00000.00
00000.00
VALUE
m³
VALUE
MIN / MAX
DELAY
SAFETY
ENABLE / DISABLE
►