OVERPRESSURE LEAK DETECTOR   

DLR-2

18/01/2002        Ihr Partner für Leckanzeigetechnik               

Sicherungsgerätebau GmbH, Siegen

- 7 -

Note: should the pressure not build up despite the gas bottle being connected, the leak must be lo-
cated and eliminated (if necessary check the pressure reducing device for the correct setting).

(8)  It must be ensured that the testing pressure of the interstitial space is not exceeded during

the whole pressure build-up process.

(9)  Functional test according to chapter 7.4.

6.2.  Setting other switching values (deviation from factory settings)

(1)  Determine the maximum operating pressure of the pipework (feed pressure).

(2)  Calculate latest alarm triggering according to chapter 3.3.

(3)  Calculate nominal pressure according to chapter 3.3

(4)  Is the testing pressure of the interstitial space greater by factor 1.3 than the nominal pres-

sure by calculated under item (3) above?
If yes, proceed with item (5)
If no: check whether the nominal pressure from item (3) can be reduced, if not, then either
increase the testing pressure or reduce the feed pressure in the inner pipe and proceed
with item (2).

(5)  Note the new values in the housing cover and proceed with setting as follows:

(6)  Unscrew the safety pin on the pressure switch.

(7)  Close both shut-off cocks of the testing device. Insert the test

pressure gauge into test coupling 51, connect pressure tank
to coupling 6.1, connect the measuring gauge to coupling 6.2
(cf. P-115 520 no. II)

(8)  Set the pressure regulation valve on the pressure reducing

device to nominal pressure.

(9)  Open the shut-off valve on the pressure reducing device.

(10) Open shut-off cock 2.2.

(11) Build up pressure to alarm pressures, check the pressure on

the pressure reducing device during the filling process (testing
pressure must not be exceeded) and readjust if necessary.
Shut-off cock 2.2 must be closed when the alarm pressure has been reached.

(12) Has the alarm been stopped?

If yes: continue with item (13)
If no: unscrew the setting screw on the pressure switch until the alarm
has been stopped, continue with item (13).

(13) Carefully tighten the setting screw on the pressure switch until the alarm is triggered.

(14) Open shut-off cock 2.2.

(15) Build up pressure until the alarm is stopped.

(16) Closs shut-off cock 2.2, open shut-off cock 2.1.

(17) Wait for alarm to be triggered, note and record the value and close shut-off cock 2.1

Safety pin

Setting
screw

Summary of Contents for DLR-2 Series

Page 1: ...Overpressure leak detector DLR 2 Z 65 26 304 Documentation DLR 2 SICHERUNGSGER TEBAU GMBH Hofstra e 10 57076 Siegen Art no 606 202 Status 11 2004...

Page 2: ...u GmbH Siegen GI 1 Contents of the documentation 1 Technical description by SGB 12 pages 2 Drawings accompanying the technical description 4 pages 3 Technical data 1 page 4 Worksheet Installing thread...

Page 3: ...4 5 3 Assembly of the leak detector 4 5 4 Assembly of the connection pipes between leak detector and pipework 5 5 5 Selection of pressure reducing device 5 5 6 Gas bottle and pressure reducing device...

Page 4: ...More extensive demands on the interstitial spaces are revealed in TRbF 131 231 part 1 the approval principles of DIBt or prEN 13160 3 2 Material to be transported Liquids hazardous to water2 3 3 Press...

Page 5: ...nto operation process by building up pressure on top of the nominal pressure usually by means of a mobile pressure tank The pressure in the interstitial space is monitored by a pressure switch in the...

Page 6: ...lated 7 A test valve must be designed on the end of the pipework away from the leak detector 8 Before inspection chambers are entered the nitrogen content must be tested and the in spection chamber fl...

Page 7: ...above ground outside must be in a protective outer pipe 6 Seal the protective pipe gas tight 7 Avoid electrostatic charge e g when introducing and pulling through pipes 5 5 Selection of pressure redu...

Page 8: ...pendix 6 Putting into operation service 6 1 Basic instructions 1 Assembly according to chapter 5 instructions given in that chapter must also be heeded here 2 The interstitial space must be flushed wi...

Page 9: ...with item 2 5 Note the new values in the housing cover and proceed with setting as follows 6 Unscrew the safety pin on the pressure switch 7 Close both shut off cocks of the testing device Insert the...

Page 10: ...sh the cause quickly and eliminate the problem 4 The operator must visually check at regular intervals that the in operation lamp is working 5 The leak detector must be disconnected from the mains for...

Page 11: ...e tasks to be carried out with the person responsible on spot 2 Heed the safety instructions regarding contact with the stored goods present 3 Check the through connections of the interstitial space c...

Page 12: ...e into coupling 51 connect the testing device to coupling 6 2 cf P 115 520 2 Set the pressure regulating valve to nominal pressure 3 Open the shut off valve on the pressure reducing device 4 Open shut...

Page 13: ...e reached in order to guarantee one year of trouble free operation 9 Once the air tightness test has been completed remove the testing device from the con nection remove the test pressure gauge from t...

Page 14: ...e of contaminated components possible gas evolution properly 9 Marking Electrical data Serial number Type description Date of manufacture month year Manufacturer s mark Statutory marks Connecting pipe...

Page 15: ...Ex Ex 71 88 57 99 99 01 6 2 09 06 11 2000 M1 102 021 022...

Page 16: ...Ex 69 71 59 55 01 6 2 09 99 99 57 57 88 88 88 06 11 2000 M2 102 021 022...

Page 17: ...2 1 6 1 6 2 6 2 2 2 51 I II bar 0 16 10 0 100 200 300 bar bar 0 0 2 2 6 6 4 4 8 8 10 10 04 12 2000 P 115 520...

Page 18: ...1 3 4 5 7 8 10 9 2 09 01 69 71 59 55 18 12 2000 SL 851 700 4 2 1...

Page 19: ...V 50 Hz 8 A min 5 V 5 mA External fuse of the leak detector max 10 A Overvoltage category 2 1 1 Terminal assignment 1 Ground 2 Phase 3 Neutral 4 5 External signal voltage in case of alarm 7 8 Potenti...

Page 20: ...thread of the basic body 3 Olive threaded fitting for plastic and metal pipes 1 Insert the reinforcing sleeve into the end of the pipe 2 Knock in the reinforcing sleeve 3 Push the union nut and the o...

Page 21: ...ay round 3 Wire clip clamp tightly using pliers and push onto the joint Screw clip push the clip over the joint and tighten it using a screwdriver care must be taken that the clip is a smooth tight fi...

Page 22: ...Applicant Sicherungsger tebau GmbH Hofstr 10 D 57076 Siegen Subject of approval Leak detector types DLR 2 11 and DLR 2 22 forming part of a leak detector device for double wall pipework in equipment...

Page 23: ...granted regardless of testing or approval reservations of other legal areas e g 1 st Directive to the device safety law low voltage guideline Law governing electromagnetic compatibility of devices EMV...

Page 24: ...essary from a technical point of view the leak detector shall be re tested 2 3 3 Initial testing of the leak detector by an authorised technical control board Initial testing shall comprise the functi...

Page 25: ...d maintained according to paragraphs 6 and 7 of the technical specification 1 The technical specification 1 should be part of the manufacturer s supply By order Strasdas Authenticated Official seal De...

Page 26: ...rtain voltage limits and defined in the 1 st Code on the Equipment Protection Law dated 11 June 1979 This declaration applies for appliances produced according to the documentation technical descripti...

Page 27: ...rom our date of sale Our warranty will be effective only if the customer submits to us the functional report or test report on initial putting into service prepared by a recognised company specialised...

Reviews: