background image

5

Step 5: Skyroute Wiring

• Keybus Connection

The Skyroute transmitter has 4 terminals marked red, black, yellow and green. Connect these four
terminals to the 4 terminals on the main control panel marked KEYBUS (aux+, aux-, yellow and
green).

• Bell IN Terminal

This terminal is used to power the cellemetry modem.This connects to the BELL + on the control
panel. No other wire should be connected to the Bell+ of the control panel or to this terminal.

Step 6: Power up the Control

Once all zone and Keybus wiring is complete, power up the control panel. First, connect the red battery lead to the positive

terminal and the black lead to negative. Then, connect the AC.

NOTE: Connect the battery before connecting the AC. You must apply AC power to the panel for at least 10

seconds, or the panel will not function. The panel will not power up on the battery connection alone.

Step 7: Programming the System

Utilize any Power keypad to program the system. Simply connect the keypad (R , B, Y, G,) terminals to the keybus

(Aux+, Aux-, Yel, Green) on the control panel.

Fill out the Programming Worksheets completely before attempting to program the system.

Step 8: Testing the System

Test the panel thoroughly to ensure that all features and functions are operating as programmed.

2.2  Terminal  Descriptions

Battery Connection

A 12V 7Ah rechargeable battery is used as a backup source of power in the event of an AC power failure. The battery

also provides additional current when the panel’s demands exceed the power output of the transformer, such as when

the Skyroute module is transmitting.

NOTE: Do not connect the battery until all other wiring is complete. Connect the battery before connecting the AC.

Connect the RED battery lead to the positive battery terminal; connect the BLACK lead to negative.

AC Terminals – AC

The panel requires a 16.5V

AC

, 40VA transformer. Connect the transformer to an unswitched AC source and connect the

transformer to these terminals.

NOTE: Do not connect the transformer until all other wiring is complete.

Auxiliary Power Terminals – AUX+ and AUX-

These terminals provide up to 550 mA of additional current at 12 V

DC

 for devices requiring power. Connect the positive

side of any device requiring power to the AUX+ terminal, the negative side to AUX- (ground). The AUX output  is protected.

This means that if too much current is drawn from these terminals (such as wiring short), the panel will  temporarily shut

off the output until the problem is corrected.

Keybus Terminals – AUX+, AUX-, YEL, GRN

The Keybus is used by the panel to communicate with the Skyroute transceiver, the programming keypad and other

modules. Each module has four Keybus terminals that must be connected to the four Keybus terminals on the panel.

Summary of Contents for Skyroute UT

Page 1: ...Installation Manual...

Page 2: ...one Line Monitor TLM 10 4 3 Swinger Shutdown 10 4 4 Skyroute Programming Sections 803 11 Activating the Skyroute Transceiver 12 Calling Connect 24 12 Skyroute Transceiver Trouble Supervision 12 Skyrou...

Page 3: ...rogrammable zone attributes Normally closed single EOL Audible Alarm Output 700mA Supervised Bell Output current limited at 3 amps 12VDC Steady or Pulsed Output EEPROM Memory Does not lose programming...

Page 4: ...ng PC5400 serial interface module or viewed with the LCD5500Z keypad and DLS 1 software Uploading and downloading capability Antenna 3 5 dB gain TNC connector Extension Kits available LAE 3 The 3 Foot...

Page 5: ...or applying AC to the panel Step 2 Mounting the Skyroute Transceiver The Skyroute Transceiver can be mounted in the upper right hand corner of the panel cabinet through the knock out The Skyroute Tra...

Page 6: ...erminal Descriptions Battery Connection A 12V 7Ah rechargeable battery is used as a backup source of power in the event of an AC power failure The battery also provides additional current when the pan...

Page 7: ...UX the negative side to PGM1 PGM2 operates similarly to PGM1 If more than 50 mA of current are required a relay must be used For a list of the programmable output options please see section the PGM Ou...

Page 8: ...el communicator to telephone lines intended for use with a fax machine These lines may incorporate a voice filter which disconnects the line if anything other than fax signals are detected resulting i...

Page 9: ...t with the mounting bracket Remove the antenna from the Skyroute module and connect the extension cable to the TNC connector on the module Secure the antenna to the TNC connector mounted on the Extens...

Page 10: ...Decimal Data A set number of programming boxes are allotted for each section requiring decimal data e g codes telephone numbers If a digit is entered for each program box the panel will automatically...

Page 11: ...iately display all the information programmed in that section Use the arrow keys to scroll through the data being displayed Scroll past the end of the data displayed or press the key to exit the secti...

Page 12: ...eiver SID System ID Sub Section 07 The chart below lists the different System ID for each of the territories For proper activation of the Skyroute Transceiver the correct SID for the territory that yo...

Page 13: ...when the Skyroute Transceiver is on stand by ready to transmit mode Troubles are indicated when LED5 flashes more than once every second Shown below is the number of flashes used to indicate each tro...

Page 14: ...09 System Trouble Output The PGM output will activate when any of the selected trouble conditions are present It will deactivate when all the selected trouble conditions are cleared The PGM attribute...

Page 15: ...wer NOTE If you program more than one PGM output as the same output type e g if PGM1 and PGM2 are both programmed as 19 Command Output 1 the settings for output attributes 1 2 and 5 must be the same T...

Page 16: ...When the keypad is again operational the default is complete Restore Panel to Default Programming Section 999 4 8 Installer s Lockout Installer code If Installer s Lockout is selected a hardware defa...

Page 17: ...M 2 015 Third System Option Code Default Option ON OFF Section ON I________I 7 TLM Enabled TLM Disabled 370 Communication Variables Default Section 003 I_______I_______I_______I Swinger Shutdown Alarm...

Page 18: ...N I_____I Option 2 B Channel Selected B Channel Not Selected OFF I_____I Option 3 Home System Only Not in Home System Operation OFF I_____I Options 4 to 8 For Future Use 07 Home SID Number 0000 I_____...

Page 19: ...to 78 if 00 is entered then that reporting code is disabled If FF is in the section then the reporting code is enabled FF is the default value 30 Alarm Reporting Codes Zones 1 8 Default Default FF I__...

Page 20: ...__I General System Trouble Restore FF I_____I_____I Fire Trouble Restoral FF I_____I_____I General System Supervisory Restore 77 Miscellaneous Maintenance Restoral Reporting Codes FF I_____I_____I Pho...

Page 21: ...20 Skyroute UT Antenna Cable Installation...

Page 22: ...Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED BLK YEL COM BELL OUT BELL IN...

Page 23: ...AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED BLK YEL CO...

Page 24: ...PC580 BELL AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 LED 5 GRN RED...

Page 25: ...t Ground Rod PC580 BELL AUX AC YEL GRN Z1 Z3 COM COM Z2 Z4 RING TIP R 1 T 1 EGND PGM 1 2 SI S0 Connection for PC Link Max Min Rx Tx Status Indicator Signal Strength Indicator LED 1 LED 2 LED 3 LED 4 L...

Page 26: ...Bell Positive Siren Trigger Bell always to ground and Bell switch to on alarm With this configuration Zx1 will be trigger every time the Bell is activated ORG RED BLK Bell Bell GND Zx COM BRG GND 120...

Page 27: ...ed Null Zone Not used Delay 1 BAzz BHzz Yes Delay 2 BAzz BHzz Yes Instant BAzz BHzz Yes Interior BAzz BHzz Yes Delay H A BAzz BHzz Yes Interior H A BAzz BHzz Yes 24 Hr Burglary BAzz BHzz Yes Standard...

Page 28: ...ower Supply Trouble YP00 YQ00 TLM Trouble Code via Skyroute LT00 General System Supervisory Restore ET00 ER00 General System Trouble Restore YX00 YZ00 TLM Restoral LR00 FTC Fail FTC Restoral YC00 YK00...

Page 29: ......

Page 30: ...erson purporting to act on its behalf to modify or to change this warranty nor to assume for it any other warranty or liability concerning this product In no event shall Sur Gard Ltd be liable for any...

Reviews: