3 Operation
LCD test
For checking the functionality of
the LCD.
Reset
All customized settings are reset
to the default settings.
3.2.3.4 Parameters menu
The Parameters menu is used to modify the default settings of
the measurements.
Accu Ni-MH
Alkaline
mAh 1850
sec 010
0 - 100%
Working order
Main test
Pre test
CH4
C3H8
C4H10
TGAS
H2
Sensors
...
...
...
...
LCD test
Reset
0.00. 0
Accu Ni-MH
Alkaline
mAh 1850
sec 010
0 - 100%
Working order
Main test
Pre test
CH4
C3H8
C4H10
TGAS
H2
Sensors
...
...
...
...
LCD test
Reset
0.00. 0
Test of working order
Setting measurement time and
limit values.
Parameter
Working order
-----------
mbar param.
bar param.
Exit
3.2.3.5 Memory menu
The Memory menu is used to delete the recorded measurements
.
No other settings are affected by this.
Memory
Clear
Exit
Main test
Setting measurement time, low-
est pressure and max. permis-
sible pressure change.
Preliminary Test
Setting measurement time, low-
est pressure and max. permis-
sible pressure change.
WO < 1.0 l/h
NWO
5.0 l/h
Working order
Meas.time 00 min
≥
Pmin = 100 mbar
dp
< 0.1 mbar
mbar param.
Meas.time 10 min
bar param.
Meas.tme 10 Min
Pmin = 0.20 bar
dp < 20 mbar