MOVITRAC
®
31.. PROFIBUS Fieldbus Interface
27
The PROFIBUS-DP
Interface
3
Bit 7: Diag.Deactivated
The frequency inverter as DP slave sets this bit permanently at zero.
This bit is set by the DP master if the MOVITRAC
®
31.. frequency inverter was identified as
non-active in the DP slave parameter set and taken off the cyclic processing.
Bit 6: Reserved
Bit 5: Diag.Sync_Mode
This bit is set by the frequency inverter as soon as it has received the Sync command.
Bit 4: Diag.Freeze_Mode
This bit is set by the frequency inverter as soon as it has received the Freeze command.
Bit 3 : Diag.WD_On
This bit is set by the MOVITRAC
®
31.. frequency inverter if the watchdog control is on.
Bit 2:
This bit is permanently set to one by the MOVITRAC
®
31.. frequency inverter.
Bit 1: Diag.Stat_Diag
If the MOVITRAC
®
31.. frequency inverter sets this bit, the DP master must pick up diagnostic
data until this bit is cleared again.
Bit 0: Diag.Prm_Req
This bit is set by the MOVITRAC
®
31.. frequency inverter if it needs to be parameterized and
configured again. This bit remains set until the frequency inverter has been parameterized with
DDLM_Set_Prm.
3 .4.3
Data in Octet 3 : Station Status 3
Fig. 32 shows the coding of octet Station Status 3 in accordance with EN 50170 V2 / DIN E 19245
Part 3. In station status 3 presently only bit 7 is relevant. Bits 0-6 are reserved.
01184AEN
Fig. 32: Coding of the octet Station Status 3 according to EN 50170 V2 / DIN E 19245 Part 3
7
LSB
MSB
6
5
4
3
2
1
0
Diag.Ext_Diag_Overflow
Octet 3: Station Status 3
Bit no.
reserved