12
MOVITRAC
®
31.. PROFIBUS Fieldbus Interface
2
Assembly / Installation
Instructions
00943AEN
Fig. 5: Bus termination at the beginning and end of a PROFIBUS segment
As the bus terminating resistors can be connected on the FFP 31 of the frequency inverter, it is not
necessary to use a type D connector with integrated terminating resistors. With the appropriate
DIP switch on the option pcb (
→
Fig. 6) set to the “on” position the bus terminating resistors (in
accordance with EN 50170 V2 / DIN E 19245 Part 3) can be connected.
The bus termination for cable type A is implemented in accordance with EN 5170 V2 /DIN E 19245
Part 3.
00303AEN
Fig. 6: Activating the bus terminating resistors
2.6
Setting the Station Address
The PROFIBUS station address is set with the DIP switches on the option pcb. PROFIBUS supports
the address range from 0 - 125. The address 126 is reserved for PROFIBUS-DP and is for setting
the address via the bus interface. This feature is, however, not supported by the MOVITRAC
®
31...
The address 127 is reserved for the broadcast service. Fig. 7 shows how the station address is set
with the DIP switches.
00304BEN
Fig. 7: Setting the PROFIBUS station address
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
MO
VI
TR
AC
®
841
E
Q
RUN
BUS
FAULT
PROFIBUS-DP/FMS
Bus termination
PROFIBUS-DP master
Fieldbus
CONTROL MODE
Fieldbus
CONTROL MODE
Fieldbus
CONTROL MODE
Analog I/O
Digital I/O
on
on
off
off
DGND
VP
R = 390 Ohm
u
R = 220 Ohm
t
R = 390 Ohm
d
Bus terminated
on = connected
off = not connected
OPEN
OPEN
1
12
24
4
3
3
________
Address 4 = factory setting
+ 0
+ 0
+ 0
x 0 =
x 0 =
x 0 =
Significance 16:
Significance 32:
Significance 64:
0
+ 0
+ 4
+ 0
x 0 =
x 0 =
x 1 =
x 0 =
Significance 1:
Significance 2:
Significance 4:
Significance 8:
Significance on