PROFINET IO configuration
Assigning the PROFINET IO device name
Manual – PROFINET IO Interfaces, Field Distributors
92
2. Set the PG/PC interface used for the online access and click the [Update list] but-
ton.
ð
In the "PROFINET device name" box, you can select the device you want to as-
sign the device name to in the project:
19210191755
3. Choose the required node.
ð
The node name is set at the factory to a default name including the MAC ID, for
example, "PnetDeviceName-00-0F-69-XX-XX-XX".
ð
Several "SEW" nodes can be differentiated by the displayed MAC addresses.
The MAC address is affixed to the MFE PROFINET IO interface. You can loc-
ate the selected MFE PROFINET IO interface using the "Flash" button, which
lets the "BUS-F" LED of the selected MFE PROFINET IO interface flash in
green or green/red. This means you can check your selection in the configura-
tion software with the actually installed PROFINET interface in the plant.
22870857/EN – 12/2016