PROFINET IO configuration
PROFINET IO configuration with topology detection
Manual – PROFINET IO Interfaces, Field Distributors
104
Detecting faulty connections
You can detect faulty connections in the "Topology view" tab.
Proceed as follows:
1. Switch to the "Topology view" tab.
2. Click the [Compare offline/online] button.
19212110347
ð
If the topology is already configured, a note appears that there is a difference
between online and offline mode.
19212114315
ð
If you switch to online mode, failures are displayed as "red" lines.
19212117259
INFORMATION
If you use a switch, you have to integrate the switch into the network as a PROFINET
device.